2005-04-11 00:00:00 | |
| |
| ************ UNSAT **************** |
| |
| |
| *** PLEASE SEE NOTES BELOW.*** |
| |
| 1)NOTE: PLEASE SEE REVIEW DATED 12/15/04 |
| PLEASE SEE THE BELOW COMMENTS FOR GEN |
| AND ASSCOIATED EQUIPMENT. |
| |
| |
| |
| 1)NOTE: PLEASE SUBMIT ALLMANUFACTURE |
| SPEC SHEETS SHOWING ALL INFORMATION FOR |
| NEW PROPOSED GENERATOR, ATS. PLEASE |
| PROVIDE PRIME MOVER INFORMATION. |
| PLEASE ALSO PLANS WILL NOW BE CHECKED |
| FOR ZONING REVIEW AS THIS WAS PREVIOUSLY |
| A COMMENT FROM ZOING FOR LOCATION OF |
| GENERATOR. |
| |
| |
| 2)NOTE: PLEASE SEE MAIN FOR GENERATOR IS |
| SHOWN IN TENANT SPACE AND NOT GROUPED OR |
| IN CLOSE PROXIMITY OF MAIN ELECTRICAL |
| ROOM OR OTHER MAINS. PLEASE SEE MAIN FOR |
| GENERATOR "WILL BE " REQUIRED IN CLOSE |
| PROXIMITY OF EXISTING MAINS 1OF 2 AND |
| 2OF 2. |
| THIS WAS PREVIOUSLY NOTED AND NOT |
| ACCEPPTABLE BY THIS OFFICE OR FIRE |
| MARSHAL'S OFFICE. |
| PLEASE PROVIDE MORE INFORMATION ON |
| THIS. |
| 230.72,230.76,230.79.ETC. |
| |
| 3)NOTE: PLEASE SEE 700.7D, 230.95,240.13 |
| FOR GROUND FAULT REQUIREMNETS AND |
| SIGNALS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE NAY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |