2005-04-11 00:00:00 
  
 ************ UNSAT ****************
  
  
 *** PLEASE SEE NOTES BELOW.***
  
 1)NOTE: PLEASE SEE REVIEW DATED 12/15/04
 PLEASE SEE THE BELOW COMMENTS FOR GEN
 AND ASSCOIATED EQUIPMENT.
  
  
  
 1)NOTE: PLEASE SUBMIT ALLMANUFACTURE
 SPEC SHEETS SHOWING ALL INFORMATION FOR
 NEW PROPOSED GENERATOR, ATS. PLEASE
 PROVIDE PRIME MOVER INFORMATION.
 PLEASE ALSO PLANS WILL NOW BE CHECKED
 FOR ZONING REVIEW AS THIS WAS PREVIOUSLY
 A COMMENT FROM ZOING FOR LOCATION OF
 GENERATOR.
  
  
 2)NOTE: PLEASE SEE MAIN FOR GENERATOR IS
 SHOWN IN TENANT SPACE AND NOT GROUPED OR
 IN CLOSE PROXIMITY OF MAIN ELECTRICAL
 ROOM OR OTHER MAINS. PLEASE SEE MAIN FOR
 GENERATOR "WILL BE " REQUIRED IN CLOSE
 PROXIMITY OF EXISTING MAINS 1OF 2 AND
 2OF 2.
 THIS WAS PREVIOUSLY NOTED AND NOT
 ACCEPPTABLE BY THIS OFFICE OR FIRE
 MARSHAL'S OFFICE.
 PLEASE PROVIDE MORE INFORMATION ON
 THIS.
 230.72,230.76,230.79.ETC.
  
 3)NOTE: PLEASE SEE 700.7D, 230.95,240.13
 FOR GROUND FAULT REQUIREMNETS AND
 SIGNALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  