2005-04-19 00:00:00LETTER FROM KAMM RE-LOCATING FIRE DAMPER
 FROM THE CEILING TO THE WALL
 PENETRATION.DUCT REVISION IS FROM
 SQUARE DUCT TO ROUND DUCT WITH NO DUCT
 SIZE OR CFM INDICATED.PROVIDE AS-BUILT
 DRAWING INDICATING SIZE OF ROUND DUCT
 AND TO WHAT EXTENT THE ROUND DUCT
 REPLACES SQUARE DUCT I.E., MAIN TRUNK
 RUN, BRANCH DUCT RUN, ETC.
  
 SUBMITTAL FOR TIE DOWN OF THE RTU &
 UPLIFT.
  