Plan Review Notes For Permit 04111389 |
Permit Number |
04111389 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-12-28 00:00:00 | FIRE REVIEW | | | | 1) BUILDING ADDRESS REQUIRED. A MINIMUM | | OF AT LEAST 6" HIGH NUMBERS ARE | | REQUIRED. | | | | 2) PLEASE REF NFPA 101 LIFE SAFETY CODE | | 2000 EDITION CHAPTER 38.3.3.2 INTERIOR | | WALL AND CEILING FINISH. | | | | 3) PLEASE INDICATE THE LOCATION OF FIRE | | EXTINGUISHERS ON FLOOR PLAN. (COULD NOT | | LOCATE) | | | | 4) SHEET FA0.1 NOTE #17, SHOULD READ | | HVAC DUCT SMOKE DETECTORS SHALL BE | | CONNECTED TO THE FIRE ALARM CONTROL | | PANEL AND INITIATE A GENERAL FIRE ALARM | | NOT A SUPERVISORY. | | | | 5) THE FIRE ALARM SYSTEM SHALL BE | | MONITORED BY A LICENSE UL LISTED FIRE | | ALARM COMPANY FOR CENTRAL STATION | | SERVICE. | | | | 6) SEPARATE SHOP DRAWINGS AND PERMIT | | APPLICATION ARE REQUIRED FOR FIRE ALARM | | AND FIRE SPRINKLER SYSTEMS REMODEL. | | | | | | NATE MCCRAY, CAPTAIN | | 561-835-2910 OR 561-805-6722 |
|