2004-12-28 00:00:00FIRE REVIEW
  
 1) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 2) PLEASE REF NFPA 101 LIFE SAFETY CODE
 2000 EDITION CHAPTER 38.3.3.2 INTERIOR
 WALL AND CEILING FINISH.
  
 3) PLEASE INDICATE THE LOCATION OF FIRE
 EXTINGUISHERS ON FLOOR PLAN. (COULD NOT
 LOCATE)
  
 4) SHEET FA0.1 NOTE #17, SHOULD READ
 HVAC DUCT SMOKE DETECTORS SHALL BE
 CONNECTED TO THE FIRE ALARM CONTROL
 PANEL AND INITIATE A GENERAL FIRE ALARM
 NOT A SUPERVISORY.
  
 5) THE FIRE ALARM SYSTEM SHALL BE
 MONITORED BY A LICENSE UL LISTED FIRE
 ALARM COMPANY FOR CENTRAL STATION
 SERVICE.
  
 6) SEPARATE SHOP DRAWINGS AND PERMIT
 APPLICATION ARE REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER SYSTEMS REMODEL.
  
  
 NATE MCCRAY, CAPTAIN