2004-12-15 00:00:00 | ************ UNSAT **************** |
| |
| 1)NOTE: PLEASE SUBMIT MANUFACTURE SPECS |
| FOR GENERATOR, ATS, AND FUEL TANKS. |
| |
| 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH SUBMITTED PANEL |
| SCHEDULE. |
| PLEASE SEE THERE ARE SOME MISSING. |
| PLEASE SEE 700.12E FOR CIRCUITING EM/EXT |
| LTS. |
| |
| |
| 3)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| |
| 4)NOTE: PLEASE SEE 110.26 FOR ELECTRICAL |
| RM CLERENCE. (153) |
| PLEASE IDENTIFY PANELS ON PLANS, ELECT |
| RM. |
| |
| 5)NOTE: PLEASE SEE MAIN FOR GENERATOR IS |
| SHOWN IN TENANT SPACE AND NOT GROUPED OR |
| IN CLOSE PROXIMITY OF MAIN ELECTRICAL |
| ROOM OR OTHER MAINS. |
| PLEASE PROVIDE MORE INFORMATION ON |
| THIS. |
| 230.72,230.76,230.79. |
| |
| 6)NOTE: PLEASE SEE 700.7D, 230.95,240.13 |
| FOR GROUND FAULT REQUIRED ON GENERATOR |
| ALSO. |
| IT IS NOTED FOR DP BUT NOT FOR MAIN 1 OF |
| 2? OR GEN MAIN? |
| |
| 7)NOTE: PLEASE SHOW TRANSFORMER |
| GROUNDING PER 250.30. |
| |
| 8)NOTE: PLEASE CLARIFY RMS 168,169, |
| APPEAR TO BE SHOWN AS ONLY "SHOWERS"?? |
| ARE THESE ALSO BATH RMS? |
| |
| 9)NOTE: PLEASE ALSO SUBMIT SPECS ON UPS |
| SYSTEM. |
| MUST SHOW A LISTING FROM A NRTL. |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY HAVE AN |
| AFFECT ON ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETED SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE NAY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |