2004-12-15 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT MANUFACTURE SPECS
 FOR GENERATOR, ATS, AND FUEL TANKS.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE.
 PLEASE SEE THERE ARE SOME MISSING.
 PLEASE SEE 700.12E FOR CIRCUITING EM/EXT
 LTS.
  
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE SEE 110.26 FOR ELECTRICAL
 RM CLERENCE. (153)
 PLEASE IDENTIFY PANELS ON PLANS, ELECT
 RM.
  
 5)NOTE: PLEASE SEE MAIN FOR GENERATOR IS
 SHOWN IN TENANT SPACE AND NOT GROUPED OR
 IN CLOSE PROXIMITY OF MAIN ELECTRICAL
 ROOM OR OTHER MAINS.
 PLEASE PROVIDE MORE INFORMATION ON
 THIS.
 230.72,230.76,230.79.
  
 6)NOTE: PLEASE SEE 700.7D, 230.95,240.13
 FOR GROUND FAULT REQUIRED ON GENERATOR
 ALSO.
 IT IS NOTED FOR DP BUT NOT FOR MAIN 1 OF
 2? OR GEN MAIN?
  
 7)NOTE: PLEASE SHOW TRANSFORMER
 GROUNDING PER 250.30.
  
 8)NOTE: PLEASE CLARIFY RMS 168,169,
 APPEAR TO BE SHOWN AS ONLY "SHOWERS"??
 ARE THESE ALSO BATH RMS?
  
 9)NOTE: PLEASE ALSO SUBMIT SPECS ON UPS
 SYSTEM.
 MUST SHOW A LISTING FROM A NRTL.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  