2005-05-23 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- TRUSS ANCHOR SCHEDULE STILL DOESN'T
 MATCH USP AND SIMPSON LATEST CATALOGUES.
 SEE CATALOGUE AND REVISE UPLIFT LOADS
 AND NUMBER OF NAILS USED. CHECK
 CONNECTOR BY CONNECTOR WITH CATALOGUE.
 OTHERWISE, PROVIDE COMPLETE ENGINEERING
 CALCULATIONS FOR NUMBER OF NAILS AND
 UPLIFT VALUES THAT DIFFER FROM THOSE
 TESTED & PUBLISHED BY THE MANUFACTURER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001 AND SEC. 1609.4.3 FBC 2001.
  
 2- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) CONNECTORS SPECIFIED ON TRUSS ANCHOR
 SCHEDULE AND PLANS AS REQUIRED BY RULE
 9B-72. GO TO WWW.FLORIDABUILDING.ORG TO
 FIND OUT ABOUT PRODUCT APPROVALS.
  
 B) AWNING WINDOW AS SHOWN ON NEW
 BATHROOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  