Plan Review Notes For Permit 04111278 |
Permit Number |
04111278 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-04-14 00:00:00 | DENIED: | | NO MECHANICAL PLANS SUBMITTED FOR REVEW. | | SEE COMMENT #3 BY JULIO GOMEZ, BUILDING | | PLANS EXAMINER. | | | | 1.PROVIDE COMBUSTION AIR CALCULATIONS | | FOR THE GAS DRYER LOCATED IN THE LAUNDRY | | ROOM. | | | | 2.PLAN SHEET A-2 INDICATES A PRE-FAB | | FIREPLACEWITH OUTSIDE AIR FOR | | COMBUSTION.TWO DIFFERENT PRE-FAB | | FIERPLACES WERE SUBMITTED.ONE OF THE | | SUBMITTALS INDICATE THE FIREPLACE IS | | VENTED ANDHAS MAKE UP AIR BUT THE OTHER | | SUBMITTAL IS A VENTLESS.PLEASE | | SUBMITTED ONLY ONE TYPE.PLEASE NOTE | | FOR THE VENTLESS FIREPLACE, COMBUSTION | | AIR CALCS ARE REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | |
|