Plan Review Notes For Permit 04111278 |
Permit Number |
04111278 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-12-02 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | | | 1} PLEASE PROVIDE A CALCULATION | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | EXISTING LOADS AND THE EXISTING OR | | PROPOSED SERVICE SPECIFICATIONS PER | | 215.15. | | | | 2} PROVIDE A PANEL SCHEDULE FOR THE NEW | | PANELS BEING INSTALLED, ALSO SHOW | | LOCATION ON PLAN. | | | | 3} PLEASE SHOW ALL RECEPTS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | -ED PER 210.8(A)(6). | | | | 4} PLEASE SEE MISSING RECEPT REQ'D FOR | | A/C EQUIPMENT. 210.63. | | | | 5} PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CURCUIT(S) ON PANEL | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | IN BEDROOMS ARE TO BE PROTECTED , | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | 6} THE A/C DISCONNECT MUST COMPLY WITH | | 110.26, IT CANNOT BE LOCATED BEHIND THE | | UNIT AS SHOWN. | | | | 7} IF THERE IS NO SMOKE DETECTOR IN THE | | MASTER BEDROOM, ONE MUSTBE ADDED PER | | 905.2.2 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|