Plan Review Notes
Plan Review Notes For Permit 04111278
Permit Number 04111278
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-02 00:00:00 
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 2} PROVIDE A PANEL SCHEDULE FOR THE NEW
 PANELS BEING INSTALLED, ALSO SHOW
 LOCATION ON PLAN.
  
 3} PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8(A)(6).
  
 4} PLEASE SEE MISSING RECEPT REQ'D FOR
 A/C EQUIPMENT. 210.63.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6} THE A/C DISCONNECT MUST COMPLY WITH
 110.26, IT CANNOT BE LOCATED BEHIND THE
 UNIT AS SHOWN.
  
 7} IF THERE IS NO SMOKE DETECTOR IN THE
 MASTER BEDROOM, ONE MUSTBE ADDED PER
 905.2.2 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved