2004-12-15 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-BRING DRAWINGS TO PALM BEACH COUNTY |
| TO |
| VERIFY IF IMPACT FEES ARE DUE OR NOT. |
| BRING BACK STAMPED DWGS & PAID RECEIPT. |
| |
| 2-SPECIFY CONCRETE SLAB JOINTS OR WWM |
| SUPPORTS AND SPACING AS REQ'D BY SEC. |
| 1909.3 FBC 2001. |
| |
| 3-WINDOW BUCK NOTES CALL FOR BEVELED |
| BUCK. BEVELED BUCK IS NOT ALLOWED. SEE |
| SEC. 1707.4.4.2 FBC 2001 FOR REQUIRED |
| INSTALLATION OF BUCKS. |
| |
| 4-PROVIDE COMPLETE FLORIDA OR LOCAL |
| PRODUCT APPROVAL FOR: |
| A) CASEMENT WINDOWS (SEE SHEET A1 |
| SPECS) |
| B) FIXED WINDOWS |
| C) SLIDING GLASS DOORS.(SEE SHEET A1). |
| D) FIREPLACE UL LISTING AND COMPLETE |
| SPECS AS REQUIRED BY SEC. 2806 FBC |
| 2001. |
| E) BBQ AS REQUIRED BY SEC. 2808 FBC |
| 2001 |
| AND OPTIONAL HOOD. |
| F) STRUCTURAL CONNECTORS USED (SIMPSON |
| OR USP). |
| G) WINDOW MULLIONS. |
| H) AWNING WINDOWS. |
| |
| 5-CLARIFY IF USING STORM SHUTTERS OR |
| MISSILE IMPACT GLAZING ON DOORS AND |
| WINDOWS (SEE WINDOW NOTES SHEET A1 AND |
| DESIGN CRITERIA AND NOTES ON SHEE A2). |
| |
| 6-IF PROVIDING STORM SHUTTERS, THEN |
| PROVIDE COMPLETE INFORMATION: KEY PLAN |
| & |
| COMPLETE INSTALLATION SCHEDULE (SEE |
| SAMPLE). ALSO, INDICATE ON SHUTTER DWGS |
| SPECIFIC MOUNTING CONDITIONS AND ANCHOR |
| TYPE AND SPACING TO BE USED ACCORDING |
| TO |
| THE DESIGN PRESSURES, EDGE DISTANCE, |
| PANEL SPAN, CONNECTION TYPE AND |
| STRUCTURE TO BE ATTACHED TO (MASONRY OR |
| CONCRETE). |
| |
| 7-UPDATE TRUSS ANCHOR SCHEDULE. SEE |
| CURRENT USP OR SIMPSON CATALOGUE FOR |
| REVISED FASTENER TYPE AND NUMBER TO |
| COMPLY WITH SEC. 1609.4.3 FBC 2001 |
| REGARDING THE STRESS INCREASE. OR |
| PROVIDE COMPLETE ENGINEERING ANALYSIS |
| FOR NUMBER AND TYPE OF FASTENER |
| DIFFERENT THAN THOSE TESTED AND |
| PUBLISHED BY THE MANUFACTURER. |
| |
| 8-A) SIZE OF FOOTING SPECIFIED ON TYP. |
| WALL SECTION DOESN'T MATCH SIZE |
| SPECIFIED ON FOUNDATION PLAN REVISE AS |
| REQUIRED. |
| B) FOOTING TO BE 12" MIN. BELOW GRADE |
| AS |
| REQUIRED BY SEC. 1804.1.3 FBC 2001. |
| |
| 9-ENERGY CALCULATIONS: A) COMPLETE |
| OWNER |
| AND CONTRACTOR INFORMATION. |
| B) CLARIFY IF USING METHOD A JUST FOR |
| THE ADDITION OR FOR ENTIRE BUILDING. |
| SEE |
| SEC. 600 CHAPTER 13, FBC 2001. |
| B) WHERE IS THE ADJACENT FRAMED WALL? |
| C) REVISE UNDER ATTIC AREA. SEE SEC. |
| 604.1.A.1 CHAPTER 13 FBC 2001. |
| D) OWNER/AGENT TO SIGN AND DATE FORM. |
| |
| 10-REVISE SPECS FOR MONO PAD AT STEEL |
| COLUMN. IT CALLS FOR #5 BARS AT 6 FEET |
| OFF CENTER EACH WAY. |
| |
| 11-REVISE DESIGN CRITERIA SPECS ON |
| SHEET |
| A2. IT CALL FOR 130MPH 3 SECOND GUST. |
| WE |
| ARE IN 140 MPH 3 SECOND GUST. |
| ALSO, CLARIFY IF USING SHUTTERS OR |
| DOORS |
| AND WINDOWS WITH MISSILE IMPACT GLASS. |
| NOTE CALLS FOR SHUTTERS AND OTHER NOTES |
| ON SAME PLANS CALL FOR MISSILE IMPACT |
| GLAZING FOR SOME TYPE OF WINDOWS. |
| |
| 12-ARCHITECT TO INCLUDE IN HIS TITLE |
| BLOCK ALL INFORMATION AS REQUIRED BY |
| CHAPTER 481 FLORIDA STATUTES AND CHAPTER |
| |
| 61G1-16.004 FLORIDA ADMINISTRATIVE |
| CODE. |
| |