Plan Review Notes
Plan Review Notes For Permit 04111262
Permit Number 04111262
Review Stop P
Sequence Number 1
Notes
Date Text
2004-12-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT D1 SANITARY RISER DIAGRAM. THIS
 IS A SOVENT SYSTEM AND AS SUCH IS AN
 ENGINEERED SYSTEM. THE STACK THAT THE
 NEW BATHROOM IS BEING TIED INTO SHALL BE
 SHOWN AS EXISTING. SHOW WHERE THE NEW
 BATHROOM IS CONNECTED TO THE SOVENT
 STACK. INDICATE THE DEVELOPED LENGTH OF
 THE PIPING FROM THE STACK TO THE
 FIXTURES. SHOW THE AERATOR AND IF THERE
 IS AN OFFSET THE DEAERATOR REQUIRED FOR
 THIS ADDED BATHROOM. SECTION 104.2.1
 2) SUBMIT A WATER RISER DIAGRAM SHOW THE
 CONNECTION TO THE EXISTING WATER IN THE
 UNIT AND ALL PIPE SIZES, WATER HAMMER
 ARRESTORS ECT. SECTION 104.3.1.1.
  
  