Plan Review Notes
Plan Review Notes For Permit 04111163
Permit Number 04111163
Review Stop P
Sequence Number 1
Notes
Date Text
2004-12-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PLANS SHALL BE ROUTED TO FDBR,
 DIVISION OF BUSINESS REGULATION, HOTEL
 AND RESTURANT DIVISION FOR REVIEW.
 RESUBMIT WITH EACH SET OF PLANS STAMPED
 AND WORKSHEETS ATTACHED. SECTION
 101.4.7
 2) GREASE INTERCEPTORS SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE
 PER WASTE ORD. #2938-96. CONTACT MR.
 COMPO AT (561) 837-4074 OR FAX # (561)
 659-7458. SUBMIT WORKSHEET FROM MR.
 COMPO WITH PLANS WHEN RESUBMITTING.
 3) ALL SHEETS - SIGNATURE REQUIRED ON
 SEAL PER FAC 61G1-16.003,
 61G15-23.002(1)(2) & FS 481.219,
 471.025. INITIALS ARE NOT APPROVED. FULL
 FIRST AND LAST NAME REQUIRED ON THE
 SIGNATURE.
 4) SHTS 1, 2, & 3 OF 3 STATES PALM BEACH
 COUNTY WATER UTILITIES DEPARTMENT. PLANS
 ARE SUBMITTED TO "CITY OF WEST PALM
 BEACH". CHANGE DETAILS TO APPROVED
 DETAILS FOR THE CITY. SECTION 104.2.1
 5) SHTS 1, 2, & 3 OF 3 NO TITLE BLOCKS
 FOR SIGNED, SEALED, DATED PLANS AS
 REQUIRED BY FAC 61G1-16.004,
 61G15-23.002(2). PLEASE SEE ALL
 INFORMATION REQUIRED TO BE IN TITLE
 BLOCK. FS 481.2055, 471.025.
 6) ALL SHEETS, TITLE BLOCK REQUIRES A
 CERTIFICATE OF AUTHROIZATION PER FAC
 61G15-23.002, FAC 61G1-16.004 & FS
 481.219, 471.025.
 7) SHT L-2 TO BE SIGNED,SEALED,DATED AND
 ALL TITLE BLOCK INFORMATION. THIS SHEET
 CALLS FOR A PUMP/LAKE SUPPLY, BUT SHT
 C-3 INDICATES A METER AND BACKFLOW FOR
 IRRIGATION. PLEASE CLARIFY. SEC
 104.2.1.
 8) SHT C-5 DUMPSTER FLOOR DRAIN
 INDICATES CONNECTION TO GREASE SYSTEM.
 STORM WATER SHALL NOT DRAIN INTO THE
 GREASE WASTE SYSTEM. PLEASE INDICATE IF
 THE DUMPSTER PAD WILL BE COVERED.
 SECTION 104.2.1 & CITY CODE SECTION
 90-125(5).
 9) SHT P-1 STORM DRAIN RISER DIAGRAM.
 HORIZONTAL DRAINAGE PIPING SHALL BE
 INSTALLED IN UNIFORM ALIGNMENT AR
 UNIFORM SLOPES. PIPING FROM 1ST ROOF
 DRAIN IS SHOWN AT 1/4"FT AND PIPING
 DOWNSTREAM OF 2ND ROOF DRAIN IS SHOWN AT
 1/2"FT. THE PIPING SHALL BE UNIFORM IN
 SLOPE. SECTION 704.1.
 10) SHT P-1 CONDENSATE LINES TO FLOOR
 DRAIN #2. FLOOR DRAINS ARE NOT APPROVED
 AS AN INDIRECT WASTE RECEPTOR. SAFE
 WASTES ARE NOT APPROVED. EITHER A FLOOR
 SINK OR A HUB DRAIN ARE APPROVED PER
 SECTION 802.3OR 802.3.2. - INDIRECT
 WASTE RECEPTORS SHALL BE LOCATED SO AS
 NOT TO CREATE A TRIPPING HAZARD.
 11) SHT P-1 DETAIL 3/P-1 AND SANT. RISER
 DIAGRAM SHOW A 2" VENT FOR THE LAV IN
 THE WOMENS TOILET ROOM, BUT SANT. PIPING
 PLAN SHOWS A 3" VENT. PLEASE CORRELATE
 PLANS TO SHOW THE SAME INFORMATION.
 SECTION 104.2.1.
 12) SHT P-2 WATER RISER DIAGRAM SHOWS
 VACUUM BREAKERS AT EACH FIXTURE. (SEE
 SHT P-3 PLUMBING LEGEND). PLEASE
 CLARIFY. (INFORMATIONAL) AIR CHAMBERS
 ARE NOT APPROVED. WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9 AT QUICK
 CLOSING VALVES ONLY. - SECTION 606.1(4)
 FULL OPEN VALVES ARE REQUIRED ON THE TOP
 OF EVERY WATER DOWN-FEED PIPE.
 13) SHT P-2 WATER FILTER UNITS MUST MEET
 THE REQUIREMENTS OF NSF-42. SECTION
 611.1. SUBMIT MANUF. SPECIFICATION
 SHEETS.
 14) SHT P-2 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLANS/PERMIT:
 A. TYPE OF GAS, (LP OR NATURAL)
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 15) SHT P-4 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL IS REQUIRED PER
 SECTION 607.3.2
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]