2004-12-27 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) PLANS SHALL BE ROUTED TO FDBR, |
| DIVISION OF BUSINESS REGULATION, HOTEL |
| AND RESTURANT DIVISION FOR REVIEW. |
| RESUBMIT WITH EACH SET OF PLANS STAMPED |
| AND WORKSHEETS ATTACHED. SECTION |
| 101.4.7 |
| 2) GREASE INTERCEPTORS SHALL BE SIZED BY |
| RODNEY COMPO, ENVIRONMENTAL COMPLIANCE |
| PER WASTE ORD. #2938-96. CONTACT MR. |
| COMPO AT (561) 837-4074 OR FAX # (561) |
| 659-7458. SUBMIT WORKSHEET FROM MR. |
| COMPO WITH PLANS WHEN RESUBMITTING. |
| 3) ALL SHEETS - SIGNATURE REQUIRED ON |
| SEAL PER FAC 61G1-16.003, |
| 61G15-23.002(1)(2) & FS 481.219, |
| 471.025. INITIALS ARE NOT APPROVED. FULL |
| FIRST AND LAST NAME REQUIRED ON THE |
| SIGNATURE. |
| 4) SHTS 1, 2, & 3 OF 3 STATES PALM BEACH |
| COUNTY WATER UTILITIES DEPARTMENT. PLANS |
| ARE SUBMITTED TO "CITY OF WEST PALM |
| BEACH". CHANGE DETAILS TO APPROVED |
| DETAILS FOR THE CITY. SECTION 104.2.1 |
| 5) SHTS 1, 2, & 3 OF 3 NO TITLE BLOCKS |
| FOR SIGNED, SEALED, DATED PLANS AS |
| REQUIRED BY FAC 61G1-16.004, |
| 61G15-23.002(2). PLEASE SEE ALL |
| INFORMATION REQUIRED TO BE IN TITLE |
| BLOCK. FS 481.2055, 471.025. |
| 6) ALL SHEETS, TITLE BLOCK REQUIRES A |
| CERTIFICATE OF AUTHROIZATION PER FAC |
| 61G15-23.002, FAC 61G1-16.004 & FS |
| 481.219, 471.025. |
| 7) SHT L-2 TO BE SIGNED,SEALED,DATED AND |
| ALL TITLE BLOCK INFORMATION. THIS SHEET |
| CALLS FOR A PUMP/LAKE SUPPLY, BUT SHT |
| C-3 INDICATES A METER AND BACKFLOW FOR |
| IRRIGATION. PLEASE CLARIFY. SEC |
| 104.2.1. |
| 8) SHT C-5 DUMPSTER FLOOR DRAIN |
| INDICATES CONNECTION TO GREASE SYSTEM. |
| STORM WATER SHALL NOT DRAIN INTO THE |
| GREASE WASTE SYSTEM. PLEASE INDICATE IF |
| THE DUMPSTER PAD WILL BE COVERED. |
| SECTION 104.2.1 & CITY CODE SECTION |
| 90-125(5). |
| 9) SHT P-1 STORM DRAIN RISER DIAGRAM. |
| HORIZONTAL DRAINAGE PIPING SHALL BE |
| INSTALLED IN UNIFORM ALIGNMENT AR |
| UNIFORM SLOPES. PIPING FROM 1ST ROOF |
| DRAIN IS SHOWN AT 1/4"FT AND PIPING |
| DOWNSTREAM OF 2ND ROOF DRAIN IS SHOWN AT |
| 1/2"FT. THE PIPING SHALL BE UNIFORM IN |
| SLOPE. SECTION 704.1. |
| 10) SHT P-1 CONDENSATE LINES TO FLOOR |
| DRAIN #2. FLOOR DRAINS ARE NOT APPROVED |
| AS AN INDIRECT WASTE RECEPTOR. SAFE |
| WASTES ARE NOT APPROVED. EITHER A FLOOR |
| SINK OR A HUB DRAIN ARE APPROVED PER |
| SECTION 802.3OR 802.3.2. - INDIRECT |
| WASTE RECEPTORS SHALL BE LOCATED SO AS |
| NOT TO CREATE A TRIPPING HAZARD. |
| 11) SHT P-1 DETAIL 3/P-1 AND SANT. RISER |
| DIAGRAM SHOW A 2" VENT FOR THE LAV IN |
| THE WOMENS TOILET ROOM, BUT SANT. PIPING |
| PLAN SHOWS A 3" VENT. PLEASE CORRELATE |
| PLANS TO SHOW THE SAME INFORMATION. |
| SECTION 104.2.1. |
| 12) SHT P-2 WATER RISER DIAGRAM SHOWS |
| VACUUM BREAKERS AT EACH FIXTURE. (SEE |
| SHT P-3 PLUMBING LEGEND). PLEASE |
| CLARIFY. (INFORMATIONAL) AIR CHAMBERS |
| ARE NOT APPROVED. WATER HAMMER ARRESTORS |
| REQUIRED BY SECTION 604.9 AT QUICK |
| CLOSING VALVES ONLY. - SECTION 606.1(4) |
| FULL OPEN VALVES ARE REQUIRED ON THE TOP |
| OF EVERY WATER DOWN-FEED PIPE. |
| 13) SHT P-2 WATER FILTER UNITS MUST MEET |
| THE REQUIREMENTS OF NSF-42. SECTION |
| 611.1. SUBMIT MANUF. SPECIFICATION |
| SHEETS. |
| 14) SHT P-2 THE FOLLOWING INFORMATION IS |
| REQUIRED FOR GAS PLANS/PERMIT: |
| A. TYPE OF GAS, (LP OR NATURAL) |
| B. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| C. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| D. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| E. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| G. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| H. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| 15) SHT P-4 WATER HEATER DETAIL, THERMAL |
| EXPANSION CONTROL IS REQUIRED PER |
| SECTION 607.3.2 |
| |
| |
| |
| REVIEW BY KEN STEVENS |