Plan Review Notes
Plan Review Notes For Permit 04111163
Permit Number 04111163
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-03 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS AS REQUIRED UNDER FAC
 61G15-23.002,61G1-16.004.
 FS 471.023,481.219
 PLEASE SEE ALL SHEETS AND FOR ALL TRADES
 WHEATHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
 **NOTE** ELECTRICAL ENGINEERS TITLE
 BLOCK IS CORRECT.
  
 2)NOTE: PLEASE SUBMIT WIND LOADING
 CALCUALTIONS FOR SITE LT POLES FOR BLDG
 REVIEW. MUST ALSO BE NOTED ON ELECTRICAL
 PLANS FOR REQUIREMENTS OF FBC 140 MPH
 WIND S.
  
 3)NOTE: PLEASE SEE "SHOW WINDOW" RECEPTS
 WILL BE REQUIRED FOR WINDOW AREAS.
 PLEASE SEE 210.62
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED DIRECTLY ABOVE A SHOW WINDOW
 FOR EACH 3.7 LINEAR M (12 FT) OR MAJOR
 FRACTION THEREOF OF SHOW WINDOW AREA
 MEASURED HORIZONTALLY AT ITS MAXIMUM
 WIDTH.
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN
 DISCONNECT TO PANLE DP AND FROM DP TO
 SUB-PANELS.EXPOSED NON?CURRENT-CARRYING
 METAL PARTS OF FIXED EQUIPMENT LIKELY TO
 BECOME ENERGIZED SHALL BE GROUNDED.
 PLEASE ALSO SEE LOCAL AMENDMENTS WHICH
 REQUIRE AN EQUIPMENT GRND PULLED WITH
 OUTSIDE CONDUITS EVEN IF EMT.
 250.110,250.122
  
 5)NOTE: PLEASE SEE CORD AND PLUG
 CONNECT-ED EQUIPMENT ABOVE CEILINGS AND
 RECEPTS ABOVE CEILINGS NOT PERMITTED.
  
  
 6)NOTE: PLEASE PROVIDE A NOTE ON PLANS
 FOR REQUIREMENTS OF GFI PROTECTION IN
 KITCHEN FOR ALL RECEPTS.
 LL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE
 LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE
 LOCATIONS SPECIFIED IN (1), (2), AND (3)
 SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL:SECTION 210.8(B)(3) IS NEW
 FOR THE 2002 CODE AND REQUIRES ALL 15-
 AND 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
 210.8B3
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE REVIEW COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY OR MAY
 NOT AFFECT ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]