2004-12-03 00:00:00 | ************** UNSAT *************** |
| |
| 1)NOTE: PLEASE SEE MISSING INFORMATION |
| ON TITLE BLOCKS AS REQUIRED UNDER FAC |
| 61G15-23.002,61G1-16.004. |
| FS 471.023,481.219 |
| PLEASE SEE ALL SHEETS AND FOR ALL TRADES |
| WHEATHER OR NOT COMMENT IS MADE BY OTHER |
| REVIEWER(S). |
| **NOTE** ELECTRICAL ENGINEERS TITLE |
| BLOCK IS CORRECT. |
| |
| 2)NOTE: PLEASE SUBMIT WIND LOADING |
| CALCUALTIONS FOR SITE LT POLES FOR BLDG |
| REVIEW. MUST ALSO BE NOTED ON ELECTRICAL |
| PLANS FOR REQUIREMENTS OF FBC 140 MPH |
| WIND S. |
| |
| 3)NOTE: PLEASE SEE "SHOW WINDOW" RECEPTS |
| WILL BE REQUIRED FOR WINDOW AREAS. |
| PLEASE SEE 210.62 |
| AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| INSTALLED DIRECTLY ABOVE A SHOW WINDOW |
| FOR EACH 3.7 LINEAR M (12 FT) OR MAJOR |
| FRACTION THEREOF OF SHOW WINDOW AREA |
| MEASURED HORIZONTALLY AT ITS MAXIMUM |
| WIDTH. |
| |
| 4)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTORS FROM MAIN |
| DISCONNECT TO PANLE DP AND FROM DP TO |
| SUB-PANELS.EXPOSED NON?CURRENT-CARRYING |
| METAL PARTS OF FIXED EQUIPMENT LIKELY TO |
| BECOME ENERGIZED SHALL BE GROUNDED. |
| PLEASE ALSO SEE LOCAL AMENDMENTS WHICH |
| REQUIRE AN EQUIPMENT GRND PULLED WITH |
| OUTSIDE CONDUITS EVEN IF EMT. |
| 250.110,250.122 |
| |
| 5)NOTE: PLEASE SEE CORD AND PLUG |
| CONNECT-ED EQUIPMENT ABOVE CEILINGS AND |
| RECEPTS ABOVE CEILINGS NOT PERMITTED. |
| |
| |
| 6)NOTE: PLEASE PROVIDE A NOTE ON PLANS |
| FOR REQUIREMENTS OF GFI PROTECTION IN |
| KITCHEN FOR ALL RECEPTS. |
| LL 125-VOLT, SINGLE-PHASE, 15- AND |
| 20-AMPERE RECEPTACLES INSTALLED IN THE |
| LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| SHALL HAVE GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION FOR |
| PERSONNEL. |
| ALL 125-VOLT, SINGLE-PHASE, 15- AND |
| 20-AMPERE RECEPTACLES INSTALLED IN THE |
| LOCATIONS SPECIFIED IN (1), (2), AND (3) |
| SHALL HAVE GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION FOR |
| PERSONNEL:SECTION 210.8(B)(3) IS NEW |
| FOR THE 2002 CODE AND REQUIRES ALL 15- |
| AND 20-AMPERE, 125-VOLT RECEPTACLES IN |
| NONDWELLING-TYPE KITCHENS TO BE GFCI |
| PROTECTED. THIS REQUIREMENT APPLIES TO |
| EACH AND EVERY 15- AND 20-AMPERE, |
| 125-VOLT KITCHEN RECEPTACLE, WHETHER OR |
| NOT THE RECEPTACLE SERVES COUNTERTOP |
| APPLIANCES. |
| 210.8B3 |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETED SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SEE ANY POSSIBLE REVIEW COMMENTS |
| FROM OTHER REVIEWER(S) WHICH MAY OR MAY |
| NOT AFFECT ELECTRICAL PLANS. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |