2004-12-23 00:00:00 | ****CORRECTIONS**** |
| PAID PLAN REVIEW |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY BEFORE A PERMIT CAN BE |
| ISSUED.THE PLANS MUST BE STAMPED AND |
| THE RECEIPT ATTACHED TO THE |
| APPLICATION. |
| 233-5025 |
| |
| 3.)STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED IN ADDITION TO TEST REPORTS |
| FAC9B-72.WWW.FLORIDABUILDING.ORG |
| |
| 4.)THE SURVEY SHOWS ONE PARCEL, |
| PROPERTY APPRAISER'S SHOWS TWO. HAS A |
| UNITY OF TITLE BEEN FILED TO JOIN THE |
| TWO PARCELS?IF IT HAS, PLEASE PROVIDE |
| EITHER A RECORDED COPY OR SUPPLY THE |
| BOOK/PAGE. THE IMPROVEMENTS CROSS OVER |
| THE PROPERTY LINE.PLEASE ADDRESS. |
| |
| 5.)NOTE -THIS PROPERTY IS LOCATED |
| IN |
| A FLOOD ZONE.A FORM BOARD ELEVATION |
| CERTIFICATE WILL BE REQUIRED BEFORE |
| CONCRETE POUR. |
| |
| 6.)SHEET C4, HANDICAP PARKING IS TO |
| COMPLY WITH CITY OF WEST PALM BEACH |
| REQUIREMENTS, SEE ATTACHED. |
| |
| 7.)PRIOR TO PERMITTING, PLEASE |
| PROVIDE |
| A SOILS INVESTIGATION REPORT. |
| |
| 8.)THE NOTE REGARDING STORM SHUTTERS |
| ON SHEET A14 IS INCORRECT.IMPACT |
| PROTECTION REQUIRED IN WINDBORNE DEBRIS |
| REGIONS, FBC1606.1.4. |
| |
| 9.)STUCCO OVER WIRE LATH IN A |
| VERTICAL |
| APPLICATION IS TO BE A MINIMUM OF 7/8", |
| FBC2504.2.2, ASTM C926.REVISE DETAILS |
| 1-A11, 7-A2.1, ANY OTHER AFFECTED |
| DETAILS. |
| |
| 10.)INDICATE THE INSTALLATION METHOD |
| IN THE NOA FOR THE MODIFIED ROOF.NOT |
| ALL METHODS ARE COMPLIANT WITH THE |
| DESIGN PRESSURE SPECIFIED.SHEETS |
| WHICH |
| ARE NOT APPLICABLE TO THIS APPLICATION |
| MAY BE DISCARDED. |
| |
| 11.) STOREFRONT NOTES, ITEM #6, STATES |
| THAT PALM BEACH COUNTY IS IN THE HIGH |
| VELOCITY HURRICANE ZONE.PALM BEACH |
| COUNTY IS NOT IN THE HIGH VELOCITY |
| ZONE. |
| PLEASE MODIFY THE NOTE TO MAKE CLEAR |
| THE |
| SPECIFICATION FOR THE STOREFRONT |
| OPTION. |
| TEST REPORTS AND PRODUCT APPROVALS ARE |
| STILL REQUIRED OUTSIDE OF THE HVHZ, |
| FBC1707.4, 1707.3. |
| |
| 12.)THE NOA FOR THE NARROW STILE DOOR |
| IS LIMITED TO 3'0 PER LEAF; SHEET A16, |
| DOOR SCHEDULE, #1, SHOWS A DIMENSION OF |
| 3'6".IS THIS THE SAME DOOR? |
| |
| 13.)DETAIL 5-S2 AND THE WOOD TRUSS |
| TIE |
| DOWN SCHEDULE REFER TO A HUGHES |
| CONNECTOR.THIS COMPANY HAS BEEN OUT |
| OF |
| BUSINESS FOR SEVERAL YEARS; PLEASE |
| REVISE THE CONNECTOR TO ONE THAT IS |
| AVAILABLE.CHECK ALL DETAILS. |
| |
| 14.)THE FASTENING FOR USP TAPL16 |
| (4-S2, WOOD TRUSS TIE DOWN SCHEDULE) |
| CONFLICTS WITH THE CATALOG (SPECIFIES |
| 11 |
| NAILS RATHER THAN 13).REVISE AND |
| CHECK |
| ALL OTHER FASTENING SPECIFICATIONS. |
| |
| 15.)3-S3 SHOWS A FRAME WALL ENCLOSING |
| THE ATTIC SPACE.TYPE V CONSTRUCTION |
| IS |
| TO BE NONCOMBUSTIBLE EXTERIOR WALLS, |
| FBC607. |
| |
| 16.)SEPARATE PERMIT REQUIRED FOR |
| DUMPSTER ENCLOSURE. |
| |
| |