Plan Review Notes
Plan Review Notes For Permit 04111163
Permit Number 04111163
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-23 00:00:00****CORRECTIONS****
 PAID PLAN REVIEW
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY BEFORE A PERMIT CAN BE
 ISSUED.THE PLANS MUST BE STAMPED AND
 THE RECEIPT ATTACHED TO THE
 APPLICATION.
 233-5025
  
 3.)STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO TEST REPORTS
 FAC9B-72.WWW.FLORIDABUILDING.ORG
  
 4.)THE SURVEY SHOWS ONE PARCEL,
 PROPERTY APPRAISER'S SHOWS TWO. HAS A
 UNITY OF TITLE BEEN FILED TO JOIN THE
 TWO PARCELS?IF IT HAS, PLEASE PROVIDE
 EITHER A RECORDED COPY OR SUPPLY THE
 BOOK/PAGE. THE IMPROVEMENTS CROSS OVER
 THE PROPERTY LINE.PLEASE ADDRESS.
  
 5.)NOTE -THIS PROPERTY IS LOCATED
 IN
 A FLOOD ZONE.A FORM BOARD ELEVATION
 CERTIFICATE WILL BE REQUIRED BEFORE
 CONCRETE POUR.
  
 6.)SHEET C4, HANDICAP PARKING IS TO
 COMPLY WITH CITY OF WEST PALM BEACH
 REQUIREMENTS, SEE ATTACHED.
  
 7.)PRIOR TO PERMITTING, PLEASE
 PROVIDE
 A SOILS INVESTIGATION REPORT.
  
 8.)THE NOTE REGARDING STORM SHUTTERS
 ON SHEET A14 IS INCORRECT.IMPACT
 PROTECTION REQUIRED IN WINDBORNE DEBRIS
 REGIONS, FBC1606.1.4.
  
 9.)STUCCO OVER WIRE LATH IN A
 VERTICAL
 APPLICATION IS TO BE A MINIMUM OF 7/8",
 FBC2504.2.2, ASTM C926.REVISE DETAILS
 1-A11, 7-A2.1, ANY OTHER AFFECTED
 DETAILS.
  
 10.)INDICATE THE INSTALLATION METHOD
 IN THE NOA FOR THE MODIFIED ROOF.NOT
 ALL METHODS ARE COMPLIANT WITH THE
 DESIGN PRESSURE SPECIFIED.SHEETS
 WHICH
 ARE NOT APPLICABLE TO THIS APPLICATION
 MAY BE DISCARDED.
  
 11.) STOREFRONT NOTES, ITEM #6, STATES
 THAT PALM BEACH COUNTY IS IN THE HIGH
 VELOCITY HURRICANE ZONE.PALM BEACH
 COUNTY IS NOT IN THE HIGH VELOCITY
 ZONE.
 PLEASE MODIFY THE NOTE TO MAKE CLEAR
 THE
 SPECIFICATION FOR THE STOREFRONT
 OPTION.
 TEST REPORTS AND PRODUCT APPROVALS ARE
 STILL REQUIRED OUTSIDE OF THE HVHZ,
 FBC1707.4, 1707.3.
  
 12.)THE NOA FOR THE NARROW STILE DOOR
 IS LIMITED TO 3'0 PER LEAF; SHEET A16,
 DOOR SCHEDULE, #1, SHOWS A DIMENSION OF
 3'6".IS THIS THE SAME DOOR?
  
 13.)DETAIL 5-S2 AND THE WOOD TRUSS
 TIE
 DOWN SCHEDULE REFER TO A HUGHES
 CONNECTOR.THIS COMPANY HAS BEEN OUT
 OF
 BUSINESS FOR SEVERAL YEARS; PLEASE
 REVISE THE CONNECTOR TO ONE THAT IS
 AVAILABLE.CHECK ALL DETAILS.
  
 14.)THE FASTENING FOR USP TAPL16
 (4-S2, WOOD TRUSS TIE DOWN SCHEDULE)
 CONFLICTS WITH THE CATALOG (SPECIFIES
 11
 NAILS RATHER THAN 13).REVISE AND
 CHECK
 ALL OTHER FASTENING SPECIFICATIONS.
  
 15.)3-S3 SHOWS A FRAME WALL ENCLOSING
 THE ATTIC SPACE.TYPE V CONSTRUCTION
 IS
 TO BE NONCOMBUSTIBLE EXTERIOR WALLS,
 FBC607.
  
 16.)SEPARATE PERMIT REQUIRED FOR
 DUMPSTER ENCLOSURE.
  
  