Plan Review Notes For Permit 04111073 |
Permit Number |
04111073 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2005-09-04 00:00:00 | *** NOTE *** | | | | ** PLANS IN TEMPORARY "F" STATUS. | | ONE SHEET (E 5.04) IN THIRD SET DID NOT | | GET SIGNED AND DATED BY THE ENGINEER OF | | RECORD. CALLED AND LEFT MESSAGE FOR | | ENGINEER TO COME IN AND SIGN SHEET. | | | | ALL THREE SETS STAMPED FOR REVISIONS OF | | LIGHTING FIXTURES FOR EGRESS ETC. | | REVISIONS FOR CIRCUITING FOR ELEVATOR | | EQUIPMENT RMS. | | REVISED SHEET: | | E-SHEETS | | 5.01,0.02,1.01,1.02,1.03,1.04,1.05, | | 1.06,1.07,1.08,2.02,4.02,5.03, 5.04 | | | | | | ** REDLINED PLANS, AN EMERGENCY BATTERY | | BACK-UP TYPE LT FIXTURE WILL BE REQUIRED | | IN MAIN ELECTRICAL RM. | | NFPA-70, 700.16, NFPA-101 7-9 | | | | NOTED NFPA-101 11-8.5(9) FOR CENTRAL | | STATION AREA. | 2005-09-03 00:00:00 | IN ELEC FOR REVIEW. |
|