2005-09-04 00:00:00*** NOTE ***
  
 ** PLANS IN TEMPORARY "F" STATUS.
 ONE SHEET (E 5.04) IN THIRD SET DID NOT
 GET SIGNED AND DATED BY THE ENGINEER OF
 RECORD. CALLED AND LEFT MESSAGE FOR
 ENGINEER TO COME IN AND SIGN SHEET.
  
 ALL THREE SETS STAMPED FOR REVISIONS OF
 LIGHTING FIXTURES FOR EGRESS ETC.
 REVISIONS FOR CIRCUITING FOR ELEVATOR
 EQUIPMENT RMS.
 REVISED SHEET:
 E-SHEETS
 5.01,0.02,1.01,1.02,1.03,1.04,1.05,
 1.06,1.07,1.08,2.02,4.02,5.03, 5.04
  
  
 ** REDLINED PLANS, AN EMERGENCY BATTERY
 BACK-UP TYPE LT FIXTURE WILL BE REQUIRED
 IN MAIN ELECTRICAL RM.
 NFPA-70, 700.16, NFPA-101 7-9
  
 NOTED NFPA-101 11-8.5(9) FOR CENTRAL
 STATION AREA.