2009-04-21 10:17:35 | ** DENIED REVISIONS** |
| |
| |
| |
| 1) NOTE: ALL LOW VOLTAGE SYSTEMS NEED TO BE PERMITTED. |
| ONLY SOME SYSTEM HAVE HAD PERMITS APPLIED. THERE ARE |
| ALSO SOME PERMITS FROM PREVIOUS SYSTEMS WHICH WERE |
| EXPIRED AND NEED TO BE RE-APPLIED. |
| THESE PLANS MAY BE REFERENCED FOR A TURN AROUND |
| PERMITS. HOWEVER VALUE FOR SCOPE OF WORK NEEDS TO BE |
| VERIFIED ALONG WITH PERMIT VALUATION FEES. |
| THE ACCESS CONTROL SYSTEM BEING PROPOSED NEEDS TO BE |
| SUBMITTED UNDER SEPARATE PLANS AND PERMITS. |
| FBC 105.1 |
| |
| 2) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE *DATA |
| ROOM*. DOES THIS ROOM MEET 645.4 1-5?. IF NOT, PLEASE |
| PLACE NOTE ON PLANS THAT *NOW WIRING METHODS IN NEC 645 |
| ARE PERMITTED IN THIS ROOM*. |
| IT IS RECOMMENDED TO VERIFY WITH ANY IT/MIS PERSONNEL |
| FROM PBAC THAT WIRING METHODS IN NEC 645 ARE NOT TO BE |
| USED. IF MEETING 645.4 THEN WIRING METHODS OF 645 ARE |
| PERMITTED. IF NOT MEETING ALL OF 645.4, 1-5, THEN ALL |
| WIRING METHODS IN CHAPTERS 1-4 ARE MANDATORY. |
| |
| |
| 3) NOTE: PLEASE PROVIDE INFORMATION OF NEW SYSTEMS |
| BEING INSTALLED FROM MANHOLE FOR LV DATA. IS THIS |
| UTILITY ENTRANCE OR FROM A SYSTEM ON THE BASE BUILDING |
| SITE. IF THIS IS FROM A UTILITY PLEASE SHOW HOW |
| GROUNDING/BONDING OF SYSTEMS IS TAKING PLACE. 800.100, |
| 250 |
| |
| |
| |
| |
| |
| NO FURTHER ELECTRICAL REVISIONS TO BE DONE UNTIL |
| APPLICATIONS ARE MADE. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |