Plan Review Notes
Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop E
Sequence Number 48
Notes
Date Text
2009-04-21 10:17:35** DENIED REVISIONS**
  
  
  
 1) NOTE: ALL LOW VOLTAGE SYSTEMS NEED TO BE PERMITTED.
 ONLY SOME SYSTEM HAVE HAD PERMITS APPLIED. THERE ARE
 ALSO SOME PERMITS FROM PREVIOUS SYSTEMS WHICH WERE
 EXPIRED AND NEED TO BE RE-APPLIED.
 THESE PLANS MAY BE REFERENCED FOR A TURN AROUND
 PERMITS. HOWEVER VALUE FOR SCOPE OF WORK NEEDS TO BE
 VERIFIED ALONG WITH PERMIT VALUATION FEES.
 THE ACCESS CONTROL SYSTEM BEING PROPOSED NEEDS TO BE
 SUBMITTED UNDER SEPARATE PLANS AND PERMITS.
 FBC 105.1
  
 2) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE *DATA
 ROOM*. DOES THIS ROOM MEET 645.4 1-5?. IF NOT, PLEASE
 PLACE NOTE ON PLANS THAT *NOW WIRING METHODS IN NEC 645
 ARE PERMITTED IN THIS ROOM*.
 IT IS RECOMMENDED TO VERIFY WITH ANY IT/MIS PERSONNEL
 FROM PBAC THAT WIRING METHODS IN NEC 645 ARE NOT TO BE
 USED. IF MEETING 645.4 THEN WIRING METHODS OF 645 ARE
 PERMITTED. IF NOT MEETING ALL OF 645.4, 1-5, THEN ALL
 WIRING METHODS IN CHAPTERS 1-4 ARE MANDATORY.
  
  
 3) NOTE: PLEASE PROVIDE INFORMATION OF NEW SYSTEMS
 BEING INSTALLED FROM MANHOLE FOR LV DATA. IS THIS
 UTILITY ENTRANCE OR FROM A SYSTEM ON THE BASE BUILDING
 SITE. IF THIS IS FROM A UTILITY PLEASE SHOW HOW
 GROUNDING/BONDING OF SYSTEMS IS TAKING PLACE. 800.100,
 250
  
  
  
  
  
 NO FURTHER ELECTRICAL REVISIONS TO BE DONE UNTIL
 APPLICATIONS ARE MADE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  