2008-04-25 16:14:09** DENIED REVISIONS **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE REVIEW NOTE #4 FROM PREVIOUS REVIEW
 AS THIS REQUESTED AND MENTIONED THAT REVISED ENERGY
 CALCULATIONS WERE NEEDED.
 PLEASE ALSO SEE THE NOTES SPECIFICALLY GAVE CODE
 SECTIONS FROM THE 2001 FBC ALONG WITH MENTION THAT THE
 CALCULATIONS WOULD ALSO BE REQUIRED UNDER THE CODE IN
 EFFECT FOR SAID PROJECT.
 PLEASE SEE THE CALCULATIONS SUBMITTED ARE FROM THE 2006
 REVISIONS TO THE 2004 FBC. THE VERSION 2.5 WAS NOT IN
 THE 2001 FBC.
 PLEASE SEE THE INFORMATION PLACED INTO THE INPUT DATA
 REPORT IS NOT ACCURATE AND DOES NOT COORDINATE WITH THE
 SUBMITTED PLANS. THE FOLLOWING ARE SOME EXAMPLES ONLY
 AND IS NOT AN EXHAUSTED LIST. PLEASE ALSO SEE THAT THE
 INPUT DATA REPORT WILL BE NOTED AS IDR IN THE REMAINDER
 OF THIS REVIEW NOTE.
  
 FOR EXAMPLE:
 PLEASE SEE THE LIGHTING FIXTURE COUNT DOES NOT
 CORRELATE WITH PLANS. THE LIGHTING FIXTURES ARE SHOWN
 AS 1 (ONE) FIXTURE AT *X* AMOUNT OF WATTS WHICH IS NOT
 ACCURATE. PLEASE SEE THE AMOUNT OF FIXTURES, THE
 WATTAGE OF FIXTURES AND THE TYPES OF FIXTURES NEED TO
 COORDINATE WITH PLANS.
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH DOES NOT SHOW ANY EXTERIOR
 LIGHTING. HOW IS THIS POSSIBLE WHEN THERE ARE CLEARLY
 EXTERIOR LIGHTS SHOWN ON PLANS?
 ** AS NOTED ABOVE, THIS IS NOT AN EXHAUSTED LIST AND
 GIVES SOME EXAMPLES ONLY.
 13-400.2,400.3.A,13-415.2.AB.1, 13-415.1.A, TABLE
 415,.415.2 ETC
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  