Plan Review Notes For Permit 04111073 |
Permit Number |
04111073 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-07-06 00:00:00 | ******** NOTES/ REVSION /PROVISO ***** | | | | 1)NOTE: PLEASE SEE CIRCUITING FOR | | ELEVATOR EQUIPMENT ROOMS FOR LTS AND | | RECEPTS SHALL MEET 620.23,620.24. | | | | 2)NOTE: PLEASE SEE EGRESS LIGHTING | | CIRCUITING SHALL BE WIRED AS ALTERNATING | | CIRCUITS TO ALLEAVIATE ANY SINGLE MEANS | | OF DISCONNECT, TRIPPING OF BRKR ETC TO | | LEAVE ANY AREA IN DARKNESS. | | LS NFPA-101 7-9 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | 3RD SET SUBMITTED BY STEVE KNIGHT FOR | | "A, S, M.E.P"S. | | STAMPED 3RD SET OF ELECTRICAL PLANS. OK | | WITH PROVISO. |
|