2007-02-06 10:31:47BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)723-2443
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWING 2ND REVIEW
 ACTION: DENIED
  
 ORNAMENTAL GLASS GUARD/ HANDRAIL SHOP DRAWING
  
 11-4.9.4
 11-4.9.4 HANDRAILS.
 STAIRWAYS SHALL HAVE HANDRAILS AT BOTH SIDES OF ALL
 STAIRS. HANDRAILS SHALL COMPLY WITH SECTION 11-4.26 AND
 SHALL HAVE THE FOLLOWING FEATURES:
  
 (2)IF HANDRAILS ARE NOT CONTINUOUS, THEY SHALL
 EXTEND AT LEAST 12 INCHES (305 MM) BEYOND THE TOP RISER
 AND AT LEAST 12 INCHES (305 MM) PLUS THE WIDTH OF ONE
 TREAD BEYOND THE BOTTOM RISER. AT THE TOP, THE
 EXTENSION SHALL BE PARALLEL WITH THE FLOOR OR GROUND
 SURFACE. AT THE BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE EXTENSION SHALL BE
 HORIZONTAL [SEE FIGURE 11-19 (C) AND FIGURE 11-19 (D)].
 HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION 11-4.4 .
  
 (3)THE CLEAR SPACE BETWEEN HANDRAILS AND WALL
 SHALL BE 1? INCHES (38 MM).
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]