Plan Review Notes
Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop M
Sequence Number 33
Notes
Date Text
2009-06-11 10:36:42M1.01 DELTA 9. SMOKE DAMPERS SHALL BE MAXIMUM 24" FROM
 SMOKE BARRIER IN ACCORDANCE WITH NFPA 90A.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]