2005-06-27 00:00:00*********IN FAILED STATUS *********
  
 ONLY TWO SETS OF PLANS SUBMITTTED .
 ONLY TWO JOBSITE SPEC BOOKS SUBMITTED.
  
 TWO SETS OF PLANS STAMPED AND NOTED WITH
 "PROVISO".
2005-06-24 00:00:00******** NOTES/ REVSION /PROVISO *****
  
 1)NOTE: PLEASE SEE CIRCUITING FOR
 ELEVATOR EQUIPMENT ROOMS FOR LTS AND
 RECEPTS SHALL MEET 620.23,620.24.
  
 2)NOTE: PLEASE SEE EGRESS LIGHTING
 CIRCUITING SHALL BE WIRED AS ALTERNATING
 CIRCUITS TO ALLEAVIATE ANY SINGLE MEANS
 OF DISCONNECT, TRIPPING OF BRKR ETC TO
 LEAVE ANY AREA IN DARKNESS.
 LS NFPA-101 7-9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]