Plan Review Notes For Permit 04111073 |
Permit Number |
04111073 |
|
Review Stop |
P |
Sequence Number |
28 |
|
Notes |
Date |
Text |
2009-03-16 16:50:49 | DENIED | | REFERENCE: | | FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P1.03 REVISION 8 SHOWS A TEE AT THE BASE OF THE | | STORM RISER WITH A CLEANOUT AND A PLUG UNDER THE SLAB. | | PLEASE CLARIFY. SECTIONS 106.1.1 & 704.5. DEAD ENDS ARE | | PROHIBITED. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|