2009-01-20 08:50:45REVIEW #: REVISION 15
 ACTION: DENIED
  
 FBC 2001 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE TOILET EXHAUST DUCTS FROM THE 1ST FLOOR TO THE
 3RD FLOOR, AS SHOWN ON PAGES M1.03 THROUGH M1.07, SHALL
 BE IN A SHAFT ENCLOSURE IN ACCORDANCE WITH 2001 FBCM
 607.4.
  
 2. DUCT PENETRATIONS OF THE SHAFT ENCLOSURE SHALL BE
 PROTECTED WITH FIRE DAMPERS IN ACCORDANCE WITH 2001
 FBCM 607.1.2. NOTE #1 ON PAGE M1.07 REFERENCES A CODE
 SECTION (607.5.3) WHICH DOES NOT EXIST IN THE 2001
 FBCM. PLEASE PROTECT PENETRATIONS IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE 2001 FLORIDA BUILDING CODE,
 MEACHANICAL.
  
 3. PAGE M1.03 SHOWS TWO DUCT PENETRATIONS FO A RATED
 STAIR ENCLOSURE. PENETRATIONS OF STAIR ENCLOSURES FOR
 PURPOSES OTHER THAN INDEPENDENT PRESSURIZATION ARE
 PROHIBITED IN ACCORDANCE WITH 2001 FBCB 1006.1.3.1.
  