Plan Review Notes For Permit 04111073 |
Permit Number |
04111073 |
|
Review Stop |
M |
Sequence Number |
28 |
|
Notes |
Date |
Text |
2009-01-20 08:50:45 | REVIEW #: REVISION 15 | | ACTION: DENIED | | | | FBC 2001 CODE FAMILY | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. THE TOILET EXHAUST DUCTS FROM THE 1ST FLOOR TO THE | | 3RD FLOOR, AS SHOWN ON PAGES M1.03 THROUGH M1.07, SHALL | | BE IN A SHAFT ENCLOSURE IN ACCORDANCE WITH 2001 FBCM | | 607.4. | | | | 2. DUCT PENETRATIONS OF THE SHAFT ENCLOSURE SHALL BE | | PROTECTED WITH FIRE DAMPERS IN ACCORDANCE WITH 2001 | | FBCM 607.1.2. NOTE #1 ON PAGE M1.07 REFERENCES A CODE | | SECTION (607.5.3) WHICH DOES NOT EXIST IN THE 2001 | | FBCM. PLEASE PROTECT PENETRATIONS IN ACCORDANCE WITH | | THE REQUIREMENTS OF THE 2001 FLORIDA BUILDING CODE, | | MEACHANICAL. | | | | 3. PAGE M1.03 SHOWS TWO DUCT PENETRATIONS FO A RATED | | STAIR ENCLOSURE. PENETRATIONS OF STAIR ENCLOSURES FOR | | PURPOSES OTHER THAN INDEPENDENT PRESSURIZATION ARE | | PROHIBITED IN ACCORDANCE WITH 2001 FBCB 1006.1.3.1. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|