Plan Review Notes
Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop M
Sequence Number 25
Notes
Date Text
2008-09-04 11:49:22PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH CITY OF WEST PALM BEACH
 AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECH. PLANS M1.01, M1.03, M1.05.
 *** DENIED ***
  
 THE FOLLOWING HAD NOT BEEN NOTICED IN PREVIOUS REVIEWS.
  
 1) PLAN M1.01 SHOWS A SUPPLY AIR DUCT AND A RETURN AIR
 TRANSFER DUCT PENETRATING THE RATED WALL TO A STAIRWAY
 ENCLOSURE (BS-3S AND BS-3N), THIS DOES NOT COMPLY WITH
 2001 FBC 1006.1.3.1. PLEASE CORRECT.
  
 2) PLAN M1.03 SHOWS A SUPPLY AIR DUCT AND A RETURN AIR
 TRANSFER DUCT PENETRATING THE RATED WALL TO A STAIRWAY
 ENCLOSURE, THIS DOES NOT COMPLY WITH 2001 FBC
 1006.1.3.1. PLEASE CORRECT.
  
 3) PLAN M1.05 SHOWS A 5" SUPPLY AIR DUCT PENETRATING A
 SMOKE BARRIER (SEE YELLOW HIGH LIGHT ON PLAN) A SMOKE
 DAMPER WILL BE REQUIRED PER 2001 FBC/M 607.3.2.
  
 4) SEE ATTACHED BUILDING REVIEW NOTES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]