Plan Review Notes For Permit 04111073 |
Permit Number |
04111073 |
|
Review Stop |
M |
Sequence Number |
25 |
|
Notes |
Date |
Text |
2008-09-04 11:49:22 | PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH CITY OF WEST PALM BEACH | | AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | REVISION TO MECH. PLANS M1.01, M1.03, M1.05. | | *** DENIED *** | | | | THE FOLLOWING HAD NOT BEEN NOTICED IN PREVIOUS REVIEWS. | | | | 1) PLAN M1.01 SHOWS A SUPPLY AIR DUCT AND A RETURN AIR | | TRANSFER DUCT PENETRATING THE RATED WALL TO A STAIRWAY | | ENCLOSURE (BS-3S AND BS-3N), THIS DOES NOT COMPLY WITH | | 2001 FBC 1006.1.3.1. PLEASE CORRECT. | | | | 2) PLAN M1.03 SHOWS A SUPPLY AIR DUCT AND A RETURN AIR | | TRANSFER DUCT PENETRATING THE RATED WALL TO A STAIRWAY | | ENCLOSURE, THIS DOES NOT COMPLY WITH 2001 FBC | | 1006.1.3.1. PLEASE CORRECT. | | | | 3) PLAN M1.05 SHOWS A 5" SUPPLY AIR DUCT PENETRATING A | | SMOKE BARRIER (SEE YELLOW HIGH LIGHT ON PLAN) A SMOKE | | DAMPER WILL BE REQUIRED PER 2001 FBC/M 607.3.2. | | | | 4) SEE ATTACHED BUILDING REVIEW NOTES. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|