Plan Review Notes For Permit 04111073 |
Permit Number |
04111073 |
|
Review Stop |
E |
Sequence Number |
21 |
|
Notes |
Date |
Text |
2006-09-22 00:00:00 | *** NOTES *** | | | | ** PLEASE SEE ALL REV'S FOR MOTORIZED | | CURTAINS , RECEPTS OK. | | | | 1) NOTE: PLEASE SUBMIT ELECTRICAL SITE | | LIGHTING UNDER A SEPARATE ELECTRICAL | | PERMIT, WHICH WILL INCLUDE ALL | | REFERENCES TO THE PANELS, CIRCUITS | | ETC.(AS SHOWN) | | PLEASE SUBMIT LIGHTING FIXTURES | | SPECS/MANUFACTURE SHEETS INDICATING THE | | LISTINGS FROM A NRTL. (UL, CSA, MET, | | ETL, TUV, ETC.) | | | | ** PLEASE KNOW, ANY LTS /POLES OVER 6FT | | SHALL ALSO SUBMIT WIND LOAD CALCULATIONS | | FOR REVIEW. | | | | 2) NOTE: PLEASE SUBMIT ACCESS CONTROL | | SYSTEM UNDER A LV PERMIT WHICH WILL SHOW | | THE SAME LOCATIONS AND NOTES AS | | INDICATED ON PLANS SUBMITTED, HOWEVER | | PLEASE ALSO SUBMIT THE SPEC/CUT SHEETS | | FOR SYSTEM AND DEVICES TO BE INSTALLED. | | PLEASE KNOW, THIS WILL ALSO BE REVIEWED | | BY THE FIRE MARSHAL'S OFFICE FOR THE | | FAIL SAFE OPERATION, UNDER POWER LOSS | | ETC. THIS INFORMATION IS SHOWN/NOTED ON | | PLANS AND SHOULD NOT BE AN ISSUE, | | HOWEVER WILL REVIEW FIRE'S REVIEW. | | | | IF THERE ARE ANY QUESTIONS ON THE ABOVE, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|