Plan Review Notes For Permit 04111073 |
Permit Number |
04111073 |
|
Review Stop |
B |
Sequence Number |
21 |
|
Notes |
Date |
Text |
2006-05-05 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 04111073 | | ADD: 300 PEMBROKE PLACE | | CONT: THE WEITZ CO | | TEL: (561723-2443 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | WALL ANCHOR CALCULATIONS REVIEW | | ACTION:DENIED | | | | 1) STANLEY M HAW P.E. RAISED SEAL TO | | READ "LICENSE" SEE ATTACHMENT RULE | | 61G15-23.001 FL ADMINISTRATIVE CODE. | | | | 2)MISSING, DBPR NOT REGISTERED: | | 471.023 F.S.CERTIFICATE OF | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | SHEET BEARING THE NAME OF AN ENGINEER | | PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING | | ENGINEERING SERVICES, SHALL INCLUDE THE | | CERTIFICATE OF AUTHORIZATION NUMBER. | | ADD THE NUMBER TO EACH SHEET.THIS MAY | | BE ADDED BY HAND. | | | | 3) SPECIFICATIONS/ SHOP DRAWINGS | | INDICATE THE USE OF POWERS LOC BOLT 1/2" | | DIAMETER AND A 1 1/2" EMBEDMENT INTO | | HOLLOW CMU. POWERS LOC BOLT IS A | | EXPANSION TYPE ANCHOR, IF EMBEDMENT IS | | TO BE 1 1/2 INCHES THE BACK OF THE BLOCK | | WILL BE BLOWN OUT SINCE BLOCK SHELL FACE | | IS 1 1/4", HAAS THIS BEEN CONSIDERED, IS | | THERE TO BE A REDUCTION? | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|