Plan Review Notes
Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop P
Sequence Number 20
Notes
Date Text
2008-07-24 11:08:59REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.03 REVISION NUMBER 3 DENIED. THERE ARE
 CHANGES/REVISIONS BETWEEN COLUUM LINES 10 THRU 11 AND B
 THRU H THAT ARE NOT CLOUDED NOR INDICATED WITH A
 REVISION NUMBER. SECTION 106.1.3.
  
 2. SHT P3.05 REVISION NUMBER 2 DENIED. THERE ARE
 CHANGES/REVISIONS SHOWN ON THE TOILET AREAS IN THE
 BASEMENT AREA "B", THE BASEMENT AREA "B"PLUMBING NEW
 WORK KEYED NOTES THAT ARE NOT CLOUDED NOR INDICATED
 WITH A REVISION NUMBER. SECTION 106.1.3.
  
 3. SHT P1.03 REVISION NUMBER 4 NOT FOUND. PLEASE CLOUD
 AND NUMBER REVISION #4 FOR REVIEW. SECTION 106.1.3.
  
 4. SHT P1.07 REVISION NUMBER 4 NOT APPROVED. SHOW THE
 PIPE SIZES FOR THE HORIZONTAL STORM SYSTEM. MINIMUM 4"
 REQUIRED FOR 1107SF, MINIMUM 5" REQUIRED FOR 1883SF,
 MINUIMUM 5" REQUIRED FOR OVERFLOW DRAIN 1107SF, &
 MINIMUM 6" REQUIRED FOR OVERFLOW DRAIN 1883SF. PLEASE
 SHOW PIPE SIZE AND/OR SLOPE OF PIPE THAT COMPLIES WITH
 SECTION 1106.3 & SECTION 1107.3.
  
 5. SHT P3.05 REVISION NUMBER 4 NOT APPROVED. THERE ARE
 CHANGES/REVISIONS ON THE PLANS THAT ARE NOT CLOUDED NOR
 INDICATED WITH A REVISION NUMBER. SECTION 106.1.3.--
 ALSO DRY HORIZONTAL VENTS ARE NOT APPROVED UPSTREAM OF
 THE WATER CLOSETS IN BOTH THE MEN'S TOILET ROOM AND
 WOMEN'S TOILET ROOM. SECTIONS 905.3 & 905.4.
  
 6. SHT P3.05 REVISION NUMBER 5 NOT APPROVED. THERE ARE
 CHANGES/REVISIONS ON THE PLANS THAT ARE NOT CLOUDED NOR
 INDICATED WITH A REVISION NUMBER. SECTION 106.1.3.--
 ALSO DRY HORIZONTAL VENTS ARE NOT APPROVED UPSTREAM OF
 THE WATER CLOSETS IN BOTH THE MEN'S TOILET ROOM AND
 WOMEN'S TOILET ROOM. SECTIONS 905.3 & 905.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved