2006-05-04 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04111073 |
| ADD: 300 PEMBROKE PLACE |
| CONT: THE WEITZ CO. |
| TEL: (561)723-2443 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVISION REVIEW: |
| ACTION: DENIED |
| ROOF SHEATHING ASSEMBLIES |
| 1) THERE ARE 2 SEPERATE PACKAGES (3)SETS |
| IN EACH DATED APRIL 26/2006 AND MARCH |
| 10/2006. |
| |
| 2) MARCH 10TH PACKAGE, DOESN'T PROVIDE |
| CALCULATIONS FOR THE FASTENING OF THE |
| DENSEDECK AND INSULATION TO THE METAL |
| DECK. |
| |
| 3) THE RATIONAL ANALYSIS PROVIDED BY |
| SLIDER ENGINEERING IS A COPY NOT AN |
| ORIGINAL, NOT A ORIGINAL SIGNATURE |
| ,RAISED SEAL OR DATE. |
| FL ADMINISTRATIVE CODE, 61G15-23.002(1) |
| |
| 4) MIKE GINSBURG P.E. SIGNED& SEALED A |
| COVER PAGE NOT INDEXING WHAT WAS |
| INCLUSIVE OF THE DOCUMENT, INDEX PAGE IS |
| THE NEXT SHEET. THERE ARE 5 SECTIONS |
| NONE INDICATE HOW MANY PAGES ARE IN EACH |
| SECTION. |
| |
| 5) INDEX PAGE INDICATES CALCULATION, |
| WHERE, ONLY RATIONAL ANYLSIS PROVIDED. |
| |
| 6) HANSON HAS DETAIL SHEETS NOT SIGNED |
| OR SEALED. |
| |
| |
| APRIL 26/06 PACKAGE |
| 7)COVER LETTER ALSO INDICATES |
| CALCULATIONS TO BE IN THE PACKAGE BUT |
| NONE WERE FOUND. |
| |
| 8) THE OLYMPIC ROOF FASTENER SUBMITTED |
| INDICATES A 137.5 STATIC WITHDRAWL |
| RESISTANCE WHEN ENBEDDED INTO 1/2" |
| PLYWOOD. ALL THE PLYWOOD WAS TO BE |
| REMOVED FROM THE DRAWINGS AND DENSEGLASS |
| WAS TO BE USED TO BRING THE BUILDING |
| BACK INTO COMPLIANCE.THE NEWEST |
| ARCHITECTURAL SHEET( DELTA 4)A4.02 |
| DETAILS 3& 4 STILL INDICATE 1/2" |
| EXTERIOR FR SHEATHING TO BE USED, PLEASE |
| CORRECT. |
| THE VALUE FOR PENETRATING THE 22 GAUGE |
| STEEL DECK IS 151.5. |
| |
| 9) THE GAF RUBEROID MODIFIED BITUMEN |
| ROOFING REPORT SUBMITTED HAS THE SBS |
| SYSTEM HIGHLIGHTED ,WHICH ONLY HAS A |
| MAXIMUM DESIGN OF -60. LIMITATION #7 |
| DOES ALLOW FOR ENHANCE FASTENING WITH |
| THE RAS 117 STANDARD. THE STANDARD WAS |
| SUBMITTED BUT THE DESIGN PROFESSIONAL |
| HASN'T PROVIDED THE CALCULATIONS FOR |
| FASTENING IN THE VARIOUS ZONES. THE |
| FASTENER EXTRAPOLATION SHEET FOR THE |
| BASE SHEET WAS SUBMITTED BUT NOT THE |
| CALCS. |