Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop P
Sequence Number 2
Notes
Date Text
2005-03-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 CITY WPB CODE
  
 A) FROM PREVIOUS REVIEW: THE COMMENT
 NUMBER SHALL REMAIN THE SAME TO AVOID
 CONFUSION.
 1) SHT C3.01 DRAIN FOR SICSSOR LIFT TO
 STORM, MORE INFORMATION IS REQUIRED FOR
 THIS DRAIN, RESPONSE NOTED, BUT PLEASE
 INDICATE WHAT WILL BE DRAINING INTO THE
 STORM LINE. IS THIS FOR STORM WATER
 ONLY? - INDICATE IF THERE IS A
 POSSIBILITY OF OIL OR GREASE
 DRAINING/DRIPPING FROM THE LIFT AND
 ENTERING THE STORM WATER.
 4) SHT A5.01 STAFF LOUNGE AND SERVING
 ROOM SINKS SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT
 INFORMATION ON DETAIL. RESPONSE NOTED
 BUT THE FOLLOWING INFORMATION IS NOT
 SHOWN. SINK DEPTH 11-4.24.4, CLEAR FLOOR
 SPACE 11-4.24.5, EXPOSED PIPES AND
 SURFACES 11-4.24.6, & FAUCETS 11-4.24.7.
 5) SHT A8.02DETAILS 1, 2, & 3 SHOW
 CLEAR FLOOR SPACE FOR ALL ACCESSIBLE
 FIXURES, TURNING AREA FOR ALL TOILET
 ROOMS. DOORS SHALL NOT OPEN INTO THE
 CLEAR FLOOR SPACE FOR ANY REQUIRED
 FIXTURE. RESPONSE NOTED, BUT THE
 FOLLOWING INFORMATION IS NOT SHOWN:
 DETAIL #2 SHOW CLEAR FLOOR SPACE FOR
 TOILET ROOMS 07 & 08 WITH TURNING AREA,
 SECTIONS 11-4.16.2, 11-4.19.3, &
 11-4.22.3. EXPOSED PIPES AND SURFACES
 11-4.19.6. ALSO IT APPEARS THAT THE
 DOORS ARE OPENING TINTO THE CLEAR FLOOR
 SPACE FOR THE LAVS. DISPENSER TO BE A
 MINIMUM OF 19" OFF THE FLOOR ON DETAIL
 11/A802. FIGURE 29(B)
 6) SHT A8.03 COFFEE CAFE ROOMS 1A03 &
 1A04 REQUIRED THAT THE PLANS BE ROUTED
 TO THE PALM BEACH COUNTY HEALTH UNIT
 DIISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW AND STAMPING PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW.
 RESPONSE NOTED, BUT THE PLANS SHALL BE
 REVIEWED AND STAMPED PRIOR TO
 RESUBMITTING FOR REVIEW CITY WPB.
 SECTION 101.4.7.
 7) SHT P102 SUBMIT CALCULATION FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, & 1107 & ALL SUBSECTIONS.
 RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS REQUIRED. SHT P1.02 4"
 RWL'S AT COL. LINES 11/R, 10-11/N,&
 10/J, MAXIMUM 1600 SF ON 4" HORIZONTAL.
 6" REQUIRED OR SLOPE TO BE INDICATED AT
 1/4"/FT. - SHT P1.03 RWL LINE AND OFD
 LINE ARE MISLABELED. - SHT P1.04 4"
 HORIZONTAL OFFSET, MAXIMUM 1600 SF,
 INDICATE SLOPE OR INCREASE TO 6". - SHT
 P1.06 MAXIMUM 1600 SF. INCREASE TO 6" OR
 INDICATE SLOPE. - SHT P1.07 RWL LINE
 FROM ROOF DRAIN AT COL. LINE 4/D SHALL
 BE RUN AT 1/4"/FT. SECTION 704.1 - SHT
 P1.08 4" OFD MISLABELED AS RWL NOT SIZED
 CORRECTLY. - PIPE SIZES MISSING ON SOME
 OFD'S AND RWL'S - SOME OFD PIPING IS
 UNDERSIZED - RWL PIPING IS MISLABELED AS
 OFD. - SOME SQUARE FOOTAGE IS NOT ADDED
 CORRECTLY. - 2" OFD PIPING NOT ADDED
 CORRECTLY. - P1.09 ALL OFD'S ARE
 MISLABELED AS RWL.
 9) SHT P3.02 WATER RISER DIAGRAM, FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER
 DOWN-FEED LINES PER SECTION 606.1(4).
 RESPONSE NOTED, BUT VALVES ARE STILL NOT
 SHOWN ON LINES TO FIXTURE L-2 ON ALL
 FLOORS.
 12) SHT P3.03 DOMESTIC WATER RISER
 DIAGRAM, WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS. RESPONSE
 NOTED, BUT WHA'S ARE STILL SHOWN IN THE
 CEILING. PLEASE LOCAATE WHERE REQUIRED
 PER 604.9 (WASH MACHINE, ICE MAKER, DISH
 WASHER IF PROVIDED),
 14) SHT P3.04 WATER FILTERS SHALL BE
 NSF-42 LISTED. SUBMIT MANUFACTURE
 SPECIFICATION SHEETS. SECTION 611.
 RESPONSE NOTED, BUT SHEETS WERE NOT
 SUBMITTED AS REQUESTED.
 16) SHT P3.04 WASH SINK WATER PIPING,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201.
 FULL OPEN VALVES REQUIRED ON ALL WATER
 DOWN-FEED LINES. SECTION 606.1(4).
 RESPONSE NOTED, BUT THE WHA'S ARE STILL
 IN THE CEILING AND THE WATER DOWN-FEED
 LINES DO NOT HAVE VALVES ON THEM.
 18) SUBMIT A STORM BUILDING DRAIN
 ISOMETRIC SHOWING ALL PIPE SIZES, RISER
 CONNECTION, AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. ALSO SHOW
 SLOPE OF PIPE. SECTION 104.3.1.1. -
 SYSTEM CUT FIRST LINE OF COMMENTS FROM
 THE TEXT. STORM ISOMETRIC REQUIRED.
 19) SUBMIT A CONDENSATED DRAIN SYSTEM
 ISOMETRIC. SHOW ALL PIPE SIZES, RISERS
 AND SHOW TERMINATION POINT FOR
 CONDENSATE. SECTION 104.3.1.1. RESPONSE
 NOTED, BUT CONDENSATE SHALL NOT DRAIN
 INTO THE SANITARY SYSTEM PER CITY CODE
 SECTION 90-125(2)(B). CONDENSATE SHALL
 DRAIN SEPARATELY OUT OF THE BUILDING AND
 CONNECT TO A CATCH BASIN, A STORM LINE,
 OR A DRYWELL. A RELIEF VENT IS REQUIRED
 AS THE CONDENSATE EXITS THE BUILDING.
 *************NEW COMMENT************
 1B) SHT P1.07 ENTIRE RUN FOR RWL FROM
 RD-2 TO 6" RWL DOWN TO LEVEL 2 TO RUN AT
 1/4"/FT SLOPE. SECTION 704.1
 2B) NOTE: ONE SET OF PLUMBING SHEETS HAS
 RED LINES SHOWING LOCATION OF COMMENTS.
 PLEASE RESUBMIT THESE SHEETS FOR
 COMPARISON.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  