Plan Review Notes
Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop P
Sequence Number 19
Notes
Date Text
2008-07-02 14:48:56REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.03 REVISION #3 INDICATED IN THE REVISION
 INDEX ON THE TITLE BLOCK IS NOT SHOWN ON THE FLOOR PLAN
 NOR ON THE RISER DIAGRAMS. ALSO NOT ALL
 CHANGES/REVISIONS ARE CLOUDED & NUMBERED WITH A
 REVISION NUMBER. SECTION 106.1.3.
  
 2. SHT P3.05 REVISION #2 INDICATED IN THE REVISION
 INDEX ON THE TITLE BLOCK IS NOT SHOWN ON THE FLOOR PLAN
 NOR ON THE RISER DIAGRAMS. ALSO NOT ALL
 CHANGES/REVISIONS ARE CLOUDED & NUMBERED WITH A
 REVISION NUMBER. SECTION 106.1.3.
  
 3. SHT P3.05 HORIZONTAL DRY VENTS ARE NOT APPROVED.
 SECTION 905.3. THIS IS SHOWN ON THE FLOOR PLAN AND THE
 RISER DIAGRAM FOR THE BASEMENT WORK.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  