2007-03-06 09:25:25REVISION PAGE SKP-2
 *** PROVISO ***
 1) 2001 FBC/M 1305.6 FILL PIPING.
 A FILL PIPE SHALL TERMINATE OUTSIDE OF A BUILDING AT A
 POINT AT LEAST 2 FEET (610 MM) FROM ANY BUILDING
 OPENING AT THE SAME OR LOWER LEVEL. A FILL PIPE SHALL
 TERMINATE IN A MANNER DESIGNED TO MINIMIZE SPILLING
 WHEN THE FILLING HOSE IS DISCONNECTED. FILL OPENING
 SHALL BE EQUIPPED WITH A TIGHT METAL COVER DESIGNED TO
 DISCOURAGE TAMPERING.
 2) 2001 FBC/M 1305.7 VENT PIPING.
 LIQUID FUEL VENT PIPES SHALL TERMINATE OUTSIDE OF
 BUILDINGS AT A POINT NOT LESS THAN 2 FEET (610 MM)
 MEASURED VERTICALLY OR HORIZONTALLY FROM ANY BUILDING
 OPENING. OUTER ENDS OF VENT PIPES SHALL TERMINATE IN A
 WEATHERPROOF VENT CAP OR FITTING OR BE PROVIDED WITH A
 WEATHERPROOF HOOD. ALL VENT CAPS SHALL HAVE A MINIMUM
 FREE OPEN AREA EQUAL TO THE CROSS-SECTIONAL AREA OF THE
 VENT PIPE AND SHALL NOT EMPLOY SCREENS FINER THAN NO. 4
 MESH. VENT PIPES SHALL TERMINATE SUFFICIENTLY ABOVE THE
 GROUND TO AVOID BEING OBSTRUCTED WITH SNOW OR ICE. VENT
 PIPES FROM TANKS CONTAINING HEATERS SHALL BE EXTENDED
 TO A LOCATION WHERE OIL VAPORS DISCHARGING FROM THE
 VENT WILL BE READILY DIFFUSED. IF THE STATIC HEAD WITH
 A VENT PIPE FILLED WITH OIL EXCEEDS 10 POUNDS PER
 SQUARE INCH (PSI) (69 KPA), THE TANK SHALL BE DESIGNED
 FOR THE MAXIMUM STATIC HEAD THAT WILL BE IMPOSED.
 LIQUID FUEL VENT PIPES SHALL NOT BE CROSS CONNECTED
 WITH FILL PIPES, LINES FROM BURNERS OR OVERFLOW LINES
 FROM AUXILIARY TANKS.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.