Plan Review Notes For Permit 04111073 |
Permit Number |
04111073 |
|
Review Stop |
E |
Sequence Number |
14 |
|
Notes |
Date |
Text |
2006-05-14 00:00:00 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE SHEET IN ONE SET | | NOTE SIGNED AND DATED BY ENGINEER. | | FS 471.025 | | | | 2) NOTE: PLEASE SEE PANEL LB14 IS NOW | | BEING MOVED INTO THE GEN ROOM? | | PLEASE CLARIFY THIS AND PLEASE SEE | | NFPA-110 FOR ELECTRICAL EQUIPMENT | | PERMITTED IN GEN RM, SHALL BE PART OF | | THE EPSS. | | | | ** PLEASE ALSO SEE COMMENTS DATED 5/4/06 | | | | PLEASE SUBMIT THE ABOVE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|