Plan Review Notes For Permit 04111073 |
Permit Number |
04111073 |
|
Review Stop |
E |
Sequence Number |
13 |
|
Notes |
Date |
Text |
2006-05-04 00:00:00 | ********** UNSAT ************ | | | | 1)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS | | IN OTHER THAN DWELLING UNITS AND GFI | | PROTECTION REQUIRED. | | | | 2) NOTE: PLEASE SEE PLANS MENTIONS FOR A | | "JUNCTION BOX" TO CONTAIN A NEW | | DISTRIBUTION PANEL. PLEASE SEE | | 240.24,408,110.26 A DISTIBUTION PANEL | | MAY NOT BE INSIDE A J-BOX. THERE IS NOT | | ENOUGH INFORMATION AND IT DOES NOT SEEM | | LIKE THIS WILL BE PERMITTED. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|