Plan Review Notes For Permit 04111073 |
Permit Number |
04111073 |
|
Review Stop |
FIRE |
Sequence Number |
12 |
|
Notes |
Date |
Text |
2007-10-23 09:52:32 | ***DENIED*** | | | | PLANS INDICATE THE PROPOSED INSTALLATION OF AN FM-200 | | FIRE SUPPRESSION SYSTEM TO AREAS ON THE THIRD LEVEL. | | PLEASE NOTE THAT REFERENCED SYSTEM SHALL BE USED IN | | ADDITION TO A COMPLETE WET AUTOMATIC FIRE SPRINKLER | | SYSTEM IN SAME THE AREAS AND NOT AS AN ALTERNATIVE | | METHOD ONLY. SEPARATE SHOP DRAWINGS AND PERMIT WILL BE | | REQUIRED PRIOR TO INSTALLATION. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|