Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop P
Sequence Number 1
Notes
Date Text
2004-12-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT C3.01 DRAIN FOR SCISSOR LIFT TO
 STORM. MORE INFORMATION IS REQUIRED FOR
 THIS DRAIN. WHAT IS IT DRAINING? SECTION
 104.2.1.
 2) SEPARATE PLANS AND PERMIT ARE
 REQUIRED FOR THE IRRIGATION. SECTION
 104.1.1.
 3) SHT A5.01 INTERIOR ELEVATION DETAILS
 NUMBERS 14/A5.01 & 17/A5.01 DO NOT
 REFLECT THE DETAIL NUMBERS SHOWN ON SHTS
 A1.05 (ROOM 12) & A1.06 (ROOM 03).
 PLEASE CORRELATE PLANS/DETAILS. SECTION
 104.2.1.
 4) SHT A5.01 STAFF LOUNGE & SERVING ROOM
 SINKS SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. SUBMIT INFORMATION
 ON DETAIL.
 5) SHT A8.02 DETAILS 1, 2, & 3 SHOW
 CLEAR FLOOR SPACE FOR ALL ACCESSIBLE
 FIXTURES, (DRINKING FOUNTAIN, URINAL
 ECT.), TURNING AREA FOR ALL TOILET
 ROOMS. DOORS SHALL NOT OPEN INTO THE
 CLEAR FLOOR SPACE FOR ANY REQUIRED
 FIXTURE. SECTIONS 11-4.15, 4-16, 4-18,
 4-19, 4-22. (DETAIL 2/8.05 ROOM 7) - TWO
 DETAILS HAVE THE NUMBER "3" AND NO
 DETAIL "4". PLEASE CLARIFY. SECTION
 104.2.1.
 6) SHT A8.03 COFFEE CAFE ROOMS 1A03 &
 1A04 REQUIRED THAT THE PLANS BE ROUTED
 TO THE PALM BEACH COUNTY HEALTH UNIT
 DIISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW AND STAMPING PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW.
 7) SHT P1.02 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS. SHOW SF OF EACH AREA WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AS WELL AS ANY SF OF AREA OF
 ROOF THAT DRAIN ONTO THE ROOF AREAS FROM
 ABOVE IN THE CALCULATIONS.
 8) SHT P3.01 SANT. RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. THE WATER
 CLOSETS FOR THE MENS TOILET ROOMS ON
 EACH FLOOR ARE NOT SHOWN ON THE RISER.
 THE HORIZONTAL DRY VENTS AT THE BASE OF
 THE STACKS ARE NOT APPROVED PER SECTION
 905.3.
 9) SHT P3.02 WATER RISER DIAGRAM, FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER
 DOWN FEED LINES PER SECTION 606.1(4).
 10) GREASE INTECEPTOR NOT APPROVED
 INSIDE OF THE BUILDING AND SHALL BE
 LOCATED OUTSIDE. GREASE INTERCEPTOR
 SHALL BE SIZED BY RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE PER WASTE ORD.
 NUMBER 2938-96. CONTACT R. COMPO AT
 (561) 835-4074. APPROVAL SHEET SHALL BE
 ATTACHED TO PLANS WHEN RESUBMITTING.
 11) SHT P3.03 FLOOR SINKS ARE REQUIRED
 FOR INDIRECT WASTE AND SHALL NOT BE A
 TRIPPING HAZARD. SECTION 802.3. - FLOOR
 DRAINS FOR DRAINING FLOORS ONLY.
 12) SHT P3.03 DOMESTIC WATER RISER
 DIAGRAM, WATERHAMMER ARRESTORS SHALL
 BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF INSTALLATION
 INSTRUCTIONS.
 13) SUBMIT A GREASE WASTE ISOMETRIC
 RISER DIAGRAM AND A SANT. RISER DIAGRAM
 FOR THIS FLOOR PLAN SHOWING WHERE IT
 CONNECTS TO THE BLDG DRAIN ISO. OR BLDG
 SEWER. SECTION 104.3.1.1.
 14) SHT P3.04 WATER FILTERS SHALL BE
 NSF-42 LISTED. SUBMIT MANUF.
 SPECIFICATION SHEETS. SECTION 611.
 15) SHT P3.04 ICE MAKER WATER SUPPLY
 REQUIRES BACKFLOW PROTECTION. SECTION
 608.3.
 16) SHT P3.04 WASH SINK WATER PIPING,
 WATER HAMMERS SHALL BE LOCATED NEAR THE
 FIXTURE NOT IN THE CEILING. PDI-WH 201.
 FULL OPEN VALVES REQUIRED PER SECTION
 606.1(4).
 17) SHT P3.05 SERVING ROOM WASTE RISER,
 ICE MACHINES TO INDIRECT WASTED. SECTION
 802.3 & 802.3.2.
 18) SUBMIT A STORM BUILDING DRAIN
 ISOMETRIC SHOWING ALL PIPE SIZES, RISER
 CONNECTION, AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. ALSO SHOW
 SLOPE OF PIPE. SECTION 104.3.1.1.
 19) SUBMIT A CONDENSATED DRAIN SYSTEM
 ISOMETRIC. SHOW ALL PIPE SIZES, RISERS
 AND SHOW TERMINATION POINT FOR
 CONDENSATE. SECTION 104.3.1.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]