Date |
Text |
2004-12-30 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| 1) SHT C3.01 DRAIN FOR SCISSOR LIFT TO |
| STORM. MORE INFORMATION IS REQUIRED FOR |
| THIS DRAIN. WHAT IS IT DRAINING? SECTION |
| 104.2.1. |
| 2) SEPARATE PLANS AND PERMIT ARE |
| REQUIRED FOR THE IRRIGATION. SECTION |
| 104.1.1. |
| 3) SHT A5.01 INTERIOR ELEVATION DETAILS |
| NUMBERS 14/A5.01 & 17/A5.01 DO NOT |
| REFLECT THE DETAIL NUMBERS SHOWN ON SHTS |
| A1.05 (ROOM 12) & A1.06 (ROOM 03). |
| PLEASE CORRELATE PLANS/DETAILS. SECTION |
| 104.2.1. |
| 4) SHT A5.01 STAFF LOUNGE & SERVING ROOM |
| SINKS SHALL COMPLY WITH SECTION 11-4.24 |
| AND ALL SUBSECTIONS. SUBMIT INFORMATION |
| ON DETAIL. |
| 5) SHT A8.02 DETAILS 1, 2, & 3 SHOW |
| CLEAR FLOOR SPACE FOR ALL ACCESSIBLE |
| FIXTURES, (DRINKING FOUNTAIN, URINAL |
| ECT.), TURNING AREA FOR ALL TOILET |
| ROOMS. DOORS SHALL NOT OPEN INTO THE |
| CLEAR FLOOR SPACE FOR ANY REQUIRED |
| FIXTURE. SECTIONS 11-4.15, 4-16, 4-18, |
| 4-19, 4-22. (DETAIL 2/8.05 ROOM 7) - TWO |
| DETAILS HAVE THE NUMBER "3" AND NO |
| DETAIL "4". PLEASE CLARIFY. SECTION |
| 104.2.1. |
| 6) SHT A8.03 COFFEE CAFE ROOMS 1A03 & |
| 1A04 REQUIRED THAT THE PLANS BE ROUTED |
| TO THE PALM BEACH COUNTY HEALTH UNIT |
| DIISION OF ENVIRONMENTAL HEALTH FOR |
| REVIEW AND STAMPING PRIOR TO |
| RESUBMITTING TO THE CITY FOR REVIEW. |
| 7) SHT P1.02 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS PER |
| SECTIONS 1106, & 1107 AND ALL |
| SUBSECTIONS. SHOW SF OF EACH AREA WITH |
| 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| PARAPETS AS WELL AS ANY SF OF AREA OF |
| ROOF THAT DRAIN ONTO THE ROOF AREAS FROM |
| ABOVE IN THE CALCULATIONS. |
| 8) SHT P3.01 SANT. RISER DIAGRAM DOES |
| NOT REFLECT THE FLOOR PLAN, NOR DOES IT |
| MEET CODE REQUIREMENTS. THE WATER |
| CLOSETS FOR THE MENS TOILET ROOMS ON |
| EACH FLOOR ARE NOT SHOWN ON THE RISER. |
| THE HORIZONTAL DRY VENTS AT THE BASE OF |
| THE STACKS ARE NOT APPROVED PER SECTION |
| 905.3. |
| 9) SHT P3.02 WATER RISER DIAGRAM, FULL |
| OPEN VALVES ARE REQUIRED ON ALL WATER |
| DOWN FEED LINES PER SECTION 606.1(4). |
| 10) GREASE INTECEPTOR NOT APPROVED |
| INSIDE OF THE BUILDING AND SHALL BE |
| LOCATED OUTSIDE. GREASE INTERCEPTOR |
| SHALL BE SIZED BY RODNEY COMPO, |
| ENVIRONMENTAL COMPLIANCE PER WASTE ORD. |
| NUMBER 2938-96. CONTACT R. COMPO AT |
| (561) 835-4074. APPROVAL SHEET SHALL BE |
| ATTACHED TO PLANS WHEN RESUBMITTING. |
| 11) SHT P3.03 FLOOR SINKS ARE REQUIRED |
| FOR INDIRECT WASTE AND SHALL NOT BE A |
| TRIPPING HAZARD. SECTION 802.3. - FLOOR |
| DRAINS FOR DRAINING FLOORS ONLY. |
| 12) SHT P3.03 DOMESTIC WATER RISER |
| DIAGRAM, WATERHAMMER ARRESTORS SHALL |
| BE LOCATED NEAR THE FIXTURE IN AN |
| "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| SHOWN. PDI-WH 201 AND MANUF INSTALLATION |
| INSTRUCTIONS. |
| 13) SUBMIT A GREASE WASTE ISOMETRIC |
| RISER DIAGRAM AND A SANT. RISER DIAGRAM |
| FOR THIS FLOOR PLAN SHOWING WHERE IT |
| CONNECTS TO THE BLDG DRAIN ISO. OR BLDG |
| SEWER. SECTION 104.3.1.1. |
| 14) SHT P3.04 WATER FILTERS SHALL BE |
| NSF-42 LISTED. SUBMIT MANUF. |
| SPECIFICATION SHEETS. SECTION 611. |
| 15) SHT P3.04 ICE MAKER WATER SUPPLY |
| REQUIRES BACKFLOW PROTECTION. SECTION |
| 608.3. |
| 16) SHT P3.04 WASH SINK WATER PIPING, |
| WATER HAMMERS SHALL BE LOCATED NEAR THE |
| FIXTURE NOT IN THE CEILING. PDI-WH 201. |
| FULL OPEN VALVES REQUIRED PER SECTION |
| 606.1(4). |
| 17) SHT P3.05 SERVING ROOM WASTE RISER, |
| ICE MACHINES TO INDIRECT WASTED. SECTION |
| 802.3 & 802.3.2. |
| 18) SUBMIT A STORM BUILDING DRAIN |
| ISOMETRIC SHOWING ALL PIPE SIZES, RISER |
| CONNECTION, AND SQUARE FOOTAGE AS IT |
| ACCUMULATES IN THE SYSTEM. ALSO SHOW |
| SLOPE OF PIPE. SECTION 104.3.1.1. |
| 19) SUBMIT A CONDENSATED DRAIN SYSTEM |
| ISOMETRIC. SHOW ALL PIPE SIZES, RISERS |
| AND SHOW TERMINATION POINT FOR |
| CONDENSATE. SECTION 104.3.1.1. |
| |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |