2004-12-30 00:00:00 | DENIED: |
| 1.PLAN SHEET A1.07, INDICATES A FUME |
| HOOD LOCATED IN ROOM 02.THIS IS NOT |
| INDICATED ON THE MECHANICAL PLAN. |
| PLEASE CLARIFY WHAT THE FUME HOOD WILL |
| BE UTILIZED FOR. |
| |
| 2.PLAN SHEET M1.01, PLAN INDICATE |
| DUCT |
| PENETRATING RATED WALL AT BS-3S & 3N, |
| AND ALSO AT THE 2HR TEMPORARY WALL. |
| PER |
| 2001 FBC(M)607.6, SPECIFIC LOCATIONS OF |
| THE FIRE DAMPERS ARE REQUIRED. |
| EXCEPTIONS FOR FIRE DAMPERS SHALL |
| COMPLY |
| WITH 2001 FBC(M)607.1.3 #3 ITEMS 1 |
| THROUGH 4.PLEASE ANNOTATE ON THE PLAN |
| SHOULD THE EXCEPTION APPLY. |
| |
| 3.PLAN SHEET M1.02, PLAN INDICATES |
| DUCTS AND OR GRILLES PENETRATING OR |
| TERMINATING AT RATED WALLS/PARTITIONS - |
| ROOM # 19,20,21,35, 1S-2 & 1S-1.2001 |
| FBC(M) 607.6. |
| |
| 4.PLAN SHEET M1.03, DUCT/GRILLE |
| PENETRATIONS OR TERMINATION AT RATED |
| WALLS/PARTITIONS - ROOM 11, 15, 1S-3S & |
| 3N. |
| |
| 5.PLAN SHEET M1.03, CLARIFY CHASE IN |
| ROOM 04, IS THIS RATED? |
| |
| 6.PLAN SHEET M1.03, CLARIFY FRESH AIR |
| INTAKE & BRANCH DUCT AT EXTERIOR WALL |
| IS |
| THIS A RELIEF GRILLE OR SUPPLY? |
| |
| 7.PLAN SHEET M1.03, PLEASE IDENTIFY |
| AHU IN THE MECHANICAL ROOM #15.PLEASE |
| IDENTIFY ALL EQUIPMENT. |
| |
| 8.PER 2001 FBC 414.5, ATRIUM SHALL BE |
| SEPARATED FROM ADJACENT SPACES WITH A 1 |
| HOUR FIRE SEPARATION.THIS IS NOT |
| INDICATED ON PLAN SHEETS A0.02 & A0.03. |
| |
| 9.PLAN SHEET M7.02 INDICATES SMOKE |
| EXHAUST AND CALCULATIONS FOR PHASE I. |
| PLEASE CLAIRFY THE FOLLOWING: |
| 1) WILL THERE BE NO COMUNICATION |
| BETWEEN |
| THE TWO PHASES UNTIL COMPLETTION OF |
| PHASE II. |
| 2) UPON COMPLETION OF PHASE II WILL |
| THEY |
| REMAIN "SEPARATED" BY WALLS & DOORS OR |
| IS THE INTENT TO HAVE THE TWO |
| STRUCTURES |
| BE "OPEN" TO EACH OTHER. |
| 3) SHOULD THE INTENT BE FOR "OPEN" THE |
| TWO STRUCTURES INTO ONE, THIS WILL THEN |
| CHANGE THE CALCULATION FOR THE "ATRUIM" |
| SMOKE EXHAUST. |
| |
| 10.PLEASE PROVIDE ADDITIONAL |
| INFORMATION ON PHASE II.IT APPEARS BY |
| DEFININTION THAT IT ALSO HAS AN ATRIUM. |
| |
| 11.PHASE II INDICATES "BASEMENT" |
| SHOULD THIS SPACE ACTUALLY BE BELOW |
| GRADE, SHOW COMPLIANCE WITH 2001 FBC(M) |
| 403.6.7. |
| |
| 12.FAN SHUTDOWN BY DUCT SMOKE |
| DETECTORS REQUIRED PER 2001 |
| FBC(M)606.2.1. |
| |
| 13.NO COMBUSTIBLE ALLOWED IN THE |
| RETURN AIR PLEUNUM, 2001 FBC(M)602.2.1. |
| |
| 14.PLANS INDICATE ROOF ACCESS.WILL |
| ANY MECHANICAL EQUIPMENT BE LOCATED IN |
| THIS AREA? |
| |
| 15.PROVIDE ADDITIONAL INFORMATION ON |
| THE GENERATOR.INDICATE DISTANCES TO |
| DOORS, WINDOWS, AND FRESH AIR INTAKES. |
| PROVIDE ELEVATION FOR THE MUFFLER |
| EXHAUST TERMINATION. |
| |
| 16.INDICATE WHAT TYPE OF "FUEL" OR |
| GAS |
| WILL BE USED FOR THE GENERATOR. |
| |
| PLEASE PROVIDE A RESPONSE LETTER |
| ADDRESSING COMMENTS TO HELP EXPEDITE |
| FUTURE REVIEW. |
| |