Plan Review Notes
Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-12-21 00:00:001. ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. WHAT HAPPENS WHEN THE EXISTING
 METAL STAIRS ARE REMOVED. WHAT AFFECT
 WILL IT HAVE.
  
 3. ELECTRONIC SWITCHES, CHAIN AND
 LOCKS REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 4. THE 20 FOOT WIDE FIRE CORRIDOR
 LOCATED ALONG THE WEST SIDE OF THE
 BUILDING IS EXPECTED TO SUPPORT WHAT
 WEIGHT.
  
 5. ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY IN 6" LETTERS.
  
 6. ALL NEW STAIRS AND RAMPS SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 7. ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 8. THE THREE STORY BUILDING PLANNED
 FOR DEMOLITION IS PRESENTLY USED FOR
 WHAT PURPOSE.
  
 9.WHAT FIRE AND LIFE SAFETY SYSTEMS
 PRESENTLY EXISTS IN THE PHASE II
 BUILDING.
  
 10. NO CUTTING OR WELDING OPERATIONS
 ARE
 TO BE PERFORMED UNTIL APPROVAL OF THE
 FIRE PREVENTION BUREAU IS OBTAINED AND
 COMPLIANCE WITH NFPA 51B, THE
 STANDARD FOR CUTTING AND WELDING
 OPERATIONS IS ACHIEVED.
  
 11. TACTILE SIGNAGE IS REQUIRED AT ALL
 EXIT STAIRS.
  
 12. THE ROOM CONTAINING THE GENERATOR
 MUST BE AT LEAST TWO HOUR FIRE RATED
 IF THE ROOM IS TO CONTAIN DIESEL
 FUEL. OPENING PROTECTIVES WILL BE
 REQUIRED.
  
 13. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 14. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 15. THE BUILDING MAY BE LOCATED IN THE
 CITY FIRE LIMITS. CERTAIN RESTRICTIONS
 MAY APPLY. PLEASE SEE APPENDIX F,
 LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING
 CODE.
  
 16. PLEASE EXPLAIN CARD READERS NOTED
 ON DOOR SCHEDULE AND INSIDE STAIRS.
 PLEASE EXPLAIN WHAT INFLUENCE THEY
 HAVE ON ANY EXITING.
  
 17. THE REQUIRED FIRE ALARM SYSTEM
 SHALL
 BE MONITORED BY A UL LISTED CENTRAL
 STATION LISTED FOR CENTRAL STATION
 SERVICE.
  
 18. KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTION.
  
 19. BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF 6" HIGH NUMBERS
 ARE REQUIRED.
  
 20. NO NON FIRE RATED MATERIALS SHALL
 BE USED AS TEMPORARY DUSTPROOF
 PARTITIONS FOR THE PHASE II
 CONSTRUCTION.
  
 21. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH
 REQUIREMENTS FOR THE GLASS RAILING.
  
 22. NO COMBUSTIBLES ALLOWED IN ANY
 RETURN AIR PLENUMS.
  
 23. PLEASE EXPLAIN MAIN INGRESS/EGRESS
 FACILITIES FOR THE BUILDING. PLEASE
 EXPLAIN HOW THE 50 % OF OCCUPANT
 LOAD EXIT DISCHARGE REQUIREMENTS IS
 BEING MET.
  
 24. A TABLE AND CHAIRS ARE NOTED
 DIRECTLY IN FRONT OF THE ATRIUM STAIR.
  
 25. PLEASE INDICATE LOCATION OF THE
 FIREFIGHTERS SMOKE CONTROL PANEL FOR
 THE ATRIUM SYSTEM. HOW WILL THE
 ATRIUM SYSTEM BE TESTED.
  
 26. THE HVAC DESIGN REQUIRES BOX ON
 PAGE M0.01 IS BLANK.
  
 27. THE ATRIUM SHALL MEET THE
 REQUIREMENTS OF THE LIFE SAFETY CODE,
 101, 2000 EDITION, SECTION 8.2.5.6.
 PLEASE EXPLAIN HOW THE CODE OR
 THE EXCEPTIONS ARE BEING MET.
  
 28. THE MANUAL CONTROLS FOR THE ATRIUM
 SHALL DISPLAY A GRAPHIC OF THE
 BUILDING.
 HOA SWITCHES ONLY WILL NOT BE ALLOWED.
 A GRAPHIC REPRESENTATION OF THE
 BUILDING SHALL BE PROVIDED.
  
 29. EXIT SIGN PLACEMENT SHALL
 NOT EXCEED 100 FEET.
  
 30. PLEASE VERIFY ALL DOOR SWINGS.
  
 31. PANIC HARDWARE REQUIRED ON EXIT
 DOORS.
  
 32. ALL SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET
 FROM ALL AIR CONDITIONER DIFFUSERS.
  
 33. PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE OF THE FIRE ALARM
 SYSTEM WILL SAY.
  
 34. WHAT WILL THE SMOKE EXHAUST PANEL
 LOOK LIKE.
  
 35. ACTIVATION OF DUCT SMOKE DETECTORS
 SHALL CAUSE THE FIRE ALARM SYSTEM TO
 ACTIVATE.
  
 36. NO PENETRATIONS PERMITTED WITHIN
 ANY REQUIRED EXIT STAIR.
  
 37. WHAT IS THE PROPOSED HEIGHT OF
 THE COLLECTION STACK RACKS.
  
 38. ARE ANY EDUCATIONAL CLASSES OR
 ACTIVITIES PLANNED FOR INSIDE THE
 BUILDING.
  
 39. ALL EXTERIOR STAIRS SHALL BE
 SLIP RESISTANT.
  
 40. THE EXITING RATIONALE SHALL BE
 FURTHER EXPLAINED.
  
 41. THE FLOOR PLANS SHOULD BE MADE
 LARGER FOR IDENTIFICATION PURPOSES.
  
 42. THE NEW PHASE ONE SQUARE FOOTAGE
 WHEN ADDED TOGETHER HAS A MATH
 ERROR. ALSO THE GROSS AREA NUMBER
 APPEARS INCORRECT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL