2004-12-21 00:00:00 | 1. ALL DEMOLITION, RENOVATION, AND |
| CONSTRUCTION TO COMPLY WITH NFPA 241. |
| |
| 2. WHAT HAPPENS WHEN THE EXISTING |
| METAL STAIRS ARE REMOVED. WHAT AFFECT |
| WILL IT HAVE. |
| |
| 3. ELECTRONIC SWITCHES, CHAIN AND |
| LOCKS REQUIRED ON FIRE LINE BACKFLOW |
| DEVICE. |
| |
| 4. THE 20 FOOT WIDE FIRE CORRIDOR |
| LOCATED ALONG THE WEST SIDE OF THE |
| BUILDING IS EXPECTED TO SUPPORT WHAT |
| WEIGHT. |
| |
| 5. ALL SHAFTS THAT ARE LARGE ENOUGH |
| FOR PERSONS TO FALL INTO MUST BE |
| MARKED SHAFTWAY IN 6" LETTERS. |
| |
| 6. ALL NEW STAIRS AND RAMPS SHALL |
| HAVE HANDRAILS ON BOTH SIDES. |
| |
| 7. ELEVATOR WARNING SIGNS ARE REQUIRED. |
| |
| 8. THE THREE STORY BUILDING PLANNED |
| FOR DEMOLITION IS PRESENTLY USED FOR |
| WHAT PURPOSE. |
| |
| 9.WHAT FIRE AND LIFE SAFETY SYSTEMS |
| PRESENTLY EXISTS IN THE PHASE II |
| BUILDING. |
| |
| 10. NO CUTTING OR WELDING OPERATIONS |
| ARE |
| TO BE PERFORMED UNTIL APPROVAL OF THE |
| FIRE PREVENTION BUREAU IS OBTAINED AND |
| COMPLIANCE WITH NFPA 51B, THE |
| STANDARD FOR CUTTING AND WELDING |
| OPERATIONS IS ACHIEVED. |
| |
| 11. TACTILE SIGNAGE IS REQUIRED AT ALL |
| EXIT STAIRS. |
| |
| 12. THE ROOM CONTAINING THE GENERATOR |
| MUST BE AT LEAST TWO HOUR FIRE RATED |
| IF THE ROOM IS TO CONTAIN DIESEL |
| FUEL. OPENING PROTECTIVES WILL BE |
| REQUIRED. |
| |
| 13. PLEASE PROVIDE PRESCRIPTIVE |
| STRENGTH |
| REQUIREMENTS FOR ALL HANDRAILS AND |
| GUARDRAILS. |
| |
| 14. PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATIONS FOR WALLS AND CEILINGS. |
| |
| 15. THE BUILDING MAY BE LOCATED IN THE |
| CITY FIRE LIMITS. CERTAIN RESTRICTIONS |
| MAY APPLY. PLEASE SEE APPENDIX F, |
| LOCAL AMENDMENTS TO THE FLORIDA |
| BUILDING |
| CODE. |
| |
| 16. PLEASE EXPLAIN CARD READERS NOTED |
| ON DOOR SCHEDULE AND INSIDE STAIRS. |
| PLEASE EXPLAIN WHAT INFLUENCE THEY |
| HAVE ON ANY EXITING. |
| |
| 17. THE REQUIRED FIRE ALARM SYSTEM |
| SHALL |
| BE MONITORED BY A UL LISTED CENTRAL |
| STATION LISTED FOR CENTRAL STATION |
| SERVICE. |
| |
| 18. KNOX-BOX LOCKING CAPS WILL BE |
| REQUIRED FOR THE FIRE DEPARTMENT |
| CONNECTION. |
| |
| 19. BUILDING ADDRESS REQUIRED ON PROPER |
| ELEVATION. A MINIMUM OF 6" HIGH NUMBERS |
| ARE REQUIRED. |
| |
| 20. NO NON FIRE RATED MATERIALS SHALL |
| BE USED AS TEMPORARY DUSTPROOF |
| PARTITIONS FOR THE PHASE II |
| CONSTRUCTION. |
| |
| 21. PLEASE PROVIDE PRESCRIPTIVE |
| STRENGTH |
| REQUIREMENTS FOR THE GLASS RAILING. |
| |
| 22. NO COMBUSTIBLES ALLOWED IN ANY |
| RETURN AIR PLENUMS. |
| |
| 23. PLEASE EXPLAIN MAIN INGRESS/EGRESS |
| FACILITIES FOR THE BUILDING. PLEASE |
| EXPLAIN HOW THE 50 % OF OCCUPANT |
| LOAD EXIT DISCHARGE REQUIREMENTS IS |
| BEING MET. |
| |
| 24. A TABLE AND CHAIRS ARE NOTED |
| DIRECTLY IN FRONT OF THE ATRIUM STAIR. |
| |
| 25. PLEASE INDICATE LOCATION OF THE |
| FIREFIGHTERS SMOKE CONTROL PANEL FOR |
| THE ATRIUM SYSTEM. HOW WILL THE |
| ATRIUM SYSTEM BE TESTED. |
| |
| 26. THE HVAC DESIGN REQUIRES BOX ON |
| PAGE M0.01 IS BLANK. |
| |
| 27. THE ATRIUM SHALL MEET THE |
| REQUIREMENTS OF THE LIFE SAFETY CODE, |
| 101, 2000 EDITION, SECTION 8.2.5.6. |
| PLEASE EXPLAIN HOW THE CODE OR |
| THE EXCEPTIONS ARE BEING MET. |
| |
| 28. THE MANUAL CONTROLS FOR THE ATRIUM |
| SHALL DISPLAY A GRAPHIC OF THE |
| BUILDING. |
| HOA SWITCHES ONLY WILL NOT BE ALLOWED. |
| A GRAPHIC REPRESENTATION OF THE |
| BUILDING SHALL BE PROVIDED. |
| |
| 29. EXIT SIGN PLACEMENT SHALL |
| NOT EXCEED 100 FEET. |
| |
| 30. PLEASE VERIFY ALL DOOR SWINGS. |
| |
| 31. PANIC HARDWARE REQUIRED ON EXIT |
| DOORS. |
| |
| 32. ALL SMOKE DETECTORS SHALL BE |
| INSTALLED A MINIMUM OF THREE FEET |
| FROM ALL AIR CONDITIONER DIFFUSERS. |
| |
| 33. PLEASE INDICATE WHAT THE VOICE |
| EVACUATION MESSAGE OF THE FIRE ALARM |
| SYSTEM WILL SAY. |
| |
| 34. WHAT WILL THE SMOKE EXHAUST PANEL |
| LOOK LIKE. |
| |
| 35. ACTIVATION OF DUCT SMOKE DETECTORS |
| SHALL CAUSE THE FIRE ALARM SYSTEM TO |
| ACTIVATE. |
| |
| 36. NO PENETRATIONS PERMITTED WITHIN |
| ANY REQUIRED EXIT STAIR. |
| |
| 37. WHAT IS THE PROPOSED HEIGHT OF |
| THE COLLECTION STACK RACKS. |
| |
| 38. ARE ANY EDUCATIONAL CLASSES OR |
| ACTIVITIES PLANNED FOR INSIDE THE |
| BUILDING. |
| |
| 39. ALL EXTERIOR STAIRS SHALL BE |
| SLIP RESISTANT. |
| |
| 40. THE EXITING RATIONALE SHALL BE |
| FURTHER EXPLAINED. |
| |
| 41. THE FLOOR PLANS SHOULD BE MADE |
| LARGER FOR IDENTIFICATION PURPOSES. |
| |
| 42. THE NEW PHASE ONE SQUARE FOOTAGE |
| WHEN ADDED TOGETHER HAS A MATH |
| ERROR. ALSO THE GROSS AREA NUMBER |
| APPEARS INCORRECT. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |