Plan Review Notes
Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop ENG
Sequence Number 1
Notes
Date Text
2004-12-08 00:00:00FAILED:
  
 1. PLEASE NOTE THAT ACCORDING TO OUR
 RECORDS, REVIEW COMMENTS FORM THE
 PUBLIC UTILITIES AND ENGINEERING HAVE
 NOT BEEN ADDRESSED, PLEASE CONTACT
 MANNY GONZALEZ AT 494-1085.
 2. PLEASE SUBMIT STORM WATER
 CALCULATIONS FOR THE PROPOSED SITE FOR
 OUR REVIEW AND APPROVAL.
 3. PLEASE SHOW THE FDCS, NOTE THAT THEY
 SHOULD BE LOCATED NOT MORE THAN
 150'FROM THE CLOSEST FIRE HYD.
 3. SHEET C3.01, SHOWS A EXIST. METER &
 A BACKFLOW, HOW THEY ARE BEING
 CONNECTED?
 4. SHEET C3.01, SHOWS 4" CALV WM, IF
 NOT BEING USED, IT SHOULD BE CAPPED AT
 GATE VALVE IN KINGS COURT.
 5. SHEET SP1.01 SHOWS WM ON SOUTH OF
 THE PROPOSED SITE CONNECTED TO A NEW
 FHYD, THEN CONNECTED TO THE 4" CALV WM
 IN KINGS COURT, SHEET C3.01 SHOWS THIS
 LINE BEING CAPPED AT PROPERTY LINE,
 PLEASE VERIFY.
 6. PLEASE INCLUDE POLLUTION PREVENTION
 PLANS IN CIVIL DRAWING.
 7. A SAFTY FENCE 8'HIGH SHOULD BE
 INSTALLED ALONG SIDE OF THE OLIVE AND
 PEMBBROKE PLACE AND MAINTAINED DURING
 THE CONST.
 8. PLEASE NOTE THAT WORK IN PUBLIC
 R.O.W REQUIRES A SEPARATE PERMIT FROM
 THE FDOT AND THE PUBLIC UTILITIES AND
 ENGINEERING,494-1086.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI