Date |
Text |
2004-12-22 00:00:00 | *************** UNSAT ***************** |
| |
| PALM BEACH ATLANTIC UNIVERSITY |
| WARREN LIBRARY |
| |
| 1)NOTE: PLEASE SEE 230.72 FOR GROUPING |
| OF MAINS. |
| PLEASE SEE LOCATION OF EHDP1. THIS WILL |
| BE REQUIRED TO BE LOCATED IN CLOSE |
| PROXIMITY OF MSB. |
| 230.72B THE ONE OR MORE ADDITIONAL |
| SERVICE DISCONNECTING MEANS FOR FIRE |
| PUMPS, FOR LEGALLY REQUIRED STANDBY, OR |
| FOR OPTIONAL STANDBY SERVICES PERMITTED |
| BY 230.2 SHALL BE INSTALLED REMOTE FROM |
| THE ONE TO SIX SERVICE DISCONNECTING |
| MEANS FOR NORMAL SERVICE TO MINIMIZE |
| THE |
| POSSIBILITY OF SIMULTANEOUS |
| INTERRUPTION |
| OF SUPPLY. HOWEVER, A RESPONSE FROM |
| NFPA |
| MENTIONS REMOTE MAY BE A CLOSE AS 10'. |
| THIS WAS BROUGHT UP IN PREVIOUS |
| MEETINGS |
| AND DECIDED THIS LOCATION WAS TO BE |
| MOVED? |
| |
| 2)NOTE: PLEASE SEE LIGHTNING PROTECTION |
| SYSTEM:IF THIS WILL BE INSTALLED |
| UNDER |
| MAIN ELECTRICAL CONTRACTORS PERMIT: |
| PLEASE SUBMIT COMPLETE PLANS FOR THIS |
| UNDER NFPA-780. IF THIS WILL BE |
| INSTALLED BY ASUB-CONTRACTOR THIS MAY |
| BE DONE UNDER SEPARATE PERMIT. PLEASE |
| ONLY REFERENCE ON PLANS AND REMOVE |
| LIGHNING AS SHOWN. |
| |
| 3)NOTE: PLEASE SEE CONDUIT FILL FOR |
| 1-1/2" CONDUIT SIZE TO HDP2 ON MSB. |
| |
| 4)NOTE: PLEASE CORRELATE PANEL |
| SCHEDULES, PANELS AND EQUIPMENT SHOWN |
| ON |
| RISER DIAGRAM. |
| PLEASE SEE THE FOLLOWING AS A SOME |
| NOTED |
| ON PLAN REVIEW. |
| |
| L2B3-NO PANEL SCHEDULE? |
| EL3- NO PANEL SCHEDULE? |
| L1B3- PANEL NOT INDICATED ON LEGEND ON |
| E5.04, MISSING INFORMATION ON RISER, |
| OCP,SIZE? |
| H2B1- 225A ON RISER 400A ON PANEL |
| SCHEDULE. |
| EH2- NOT ON RISER? |
| H1B2- 400A ON PANEL SCHEDULE, 225A ON |
| RISER. |
| L4A1- 250A ON RISER 225A ON PANEL |
| SCHEDULE. |
| L1A2- 125A ON PANEL SCHEDULE,225A ON |
| RISER. |
| L2B1- 250A ON RISER AND 400A ON PANEL |
| SCHEDULE. |
| |
| 5)NOTE: PLEASE SEE SIZE OF OCP FOR |
| TRANSFORMER T1A1, MAX 125% 450.3 |
| |
| 6)NOTE: PLEASE SEE A MCB WILL BE |
| REQUIRED FOR L3A2 ON THE LOAD SIDE OF |
| THE TRANSFORMER. PLEASE SEE LOADS ARE |
| NOT SPECIFIC.IN ADDITION TO THE |
| REQUIREMENTS OF 408.13, A POWER |
| PANELBOARD WITH SUPPLY CONDUCTORS THAT |
| INCLUDE A NEUTRAL AND HAVING MORE THAN |
| 10 PERCENT OF ITS OVERCURRENT DEVICES |
| PROTECTING BRANCH CIRCUITS RATED 30 |
| AMPERES OR LESS SHALL BE PROTECTED BY |
| AN |
| OVERCURRENT PROTECTIVE DEVICE HAVING A |
| RATING NOT GREATER THAN THAT OF THE |
| PANELBOARD. THE OVERCURRENT PROTECTIVE |
| DEVICE SHALL BE LOCATED WITHIN OR AT |
| ANY |
| POINT ON THE SUPPLY SIDE OF THE |
| PANELBOARD. |
| |
| 7)NOTE: PLEASE SUBMIT COMPLETED |
| INFORMATION FOR FIRE PUMP. |
| PLEASE SEE 695.4B1 THE OVERCURRENT |
| PROTECTIVE DEVICE(S) SHALL BE SELECTED |
| OR SET TO CARRY INDEFINITELY THE SUM OF |
| THE LOCKED-ROTOR CURRENT OF THE FIRE |
| PUMP MOTOR(S) AND THE PRESSURE |
| MAINTENANCE PUMP MOTOR(S) AND THE |
| FULL-LOAD CURRENT OF THE ASSOCIATED |
| FIRE |
| PUMP ACCESSORY EQUIPMENT WHEN CONNECTED |
| TO THIS POWER SUPPLY. |
| PLEASE SEE SECONDARY OCP IS NOT |
| PERMITTED AS SHOWN.695.5BTHE PRIMARY |
| OVERCURRENT PROTECTIVE DEVICE(S) SHALL |
| BE SELECTED OR SET TO CARRY |
| INDEFINITELY |
| THE SUM OF THE LOCKED-ROTOR CURRENT OF |
| THE FIRE PUMP MOTOR(S) AND THE PRESSURE |
| MAINTENANCE PUMP MOTOR(S) AND THE |
| FULL-LOAD CURRENT OF THE ASSOCIATED |
| FIRE |
| PUMP ACCESSORY EQUIPMENT WHEN CONNECTED |
| TO THIS POWER SUPPLY. SECONDARY |
| OVERCURRENT PROTECTION SHALL NOT BE |
| PERMITTED. |
| |
| 8)NOTE: PLEASE SEE NO INFORMATION WAS |
| GIVEN FOR FIRE PUMP CONTROLLER. PLEASE |
| SEE RISER DOES NOT INDICATE ANY METHOD |
| OF TRANSFER OF POWER FROM FPL AND |
| GENERATOR FOR FIRE PUMP? |
| PLEASE COMPLETE AND SUBMIT ALL |
| MANUFACTURE SPECS FOR FIRE PUMP, FIRE |
| PUMP CONTROLLER, ATS, GENERATOR, FUEL |
| ETC. |
| |
| 9)NOTE: PLEASE SEE SOME ELECTRICAL ROOM |
| LAYOUTS DO NOT MEET 110.26 FOR CODE |
| COMPLIANCE. |
| PLEASE SEE PLANS AND ADJUST. |
| |
| 10)NOTE: PLEASE SHOW GROUNDING |
| ELECTRODE |
| SYSTEM PER 250.50. COULD NOT LOCATE ANY |
| ON ELECTRICAL PLANS SUBMITTED. |
| |
| 11)NOTE: PLEASE SHOW GROUNDING FOR ALL |
| TRANSFORMERS OR A COMMON DETAIL FOR |
| TRANSFORMERS PER 250.30 |
| |
| 12)NOTE: PLEASE SEE NOTES FROM ALL |
| OTHER |
| REVIEWERS ON THE SCOPE OF WORK FOR |
| PAHSE |
| ONE AND TWO AND POSSIBLE SEPARATE |
| PERMITS FOR EACH OR ALL WORK MUST BE |
| COMPLETED UNDER ONE PHASE. |
| PHASE ONE WILL NOTBE PERMITTED TO |
| HAVE |
| POWER WITH FEEDERS ETC FOR PHASE TWO |
| NOT |
| INSTALLED AND PULLED/SAFED OFF ETC. |
| PLEASE SEE THAT A MEETING TO DICUSS THE |
| PROCESS OF PHASES, COMPLETIONS, C/O'S |
| ETC. |
| |
| 13)NOTE: PLEASE SEE DUE TO COMPLETE |
| INFORMATION NOT SUBMITTED AT THIS TIME |
| A |
| COMPLETE REVIEW FOR CODE COMPLIANCE CAN |
| NOT BE DONE. |
| |
| PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| |
| |
| |
| IF SYSTEM IS |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |