2004-12-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)310-2723
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 NOTES: SINCE THIS PROJECT IS A
 THRESHOLD
  
 BUILDING (3) COPIES OF ALL PLANS,
 PRODUCT APPROVALS & SUBMITTALS WILL BE
 REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY
 WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PHASING I/ II. THERE ARE VARIOUS ISSUES
 THAT WILL NEED TO BE ADDRESSED BEFORE
 PHASING WILL BE APPROVED VS. APPROVAL
 FOR A SEPERATE PERMIT FOR A REMODELING
 AND ADDITION PREMIT FOR THE WORK TO BE
 ACCOMPLISHED UNDER PHASE II.
 3A) I DO NOT BELIEVE AFTER THE WORK
 COMPLETED UNDER PHASE I AND A TCO(
 PARTIAL AND OR CONDITIONAL CERTIFICATE
 OF OCCUPANCY)IS ISSUED, THE WORK ON THE
 SECOND PHASE CAN BE COMPLETED WITHIN
 THE
 30 DAYS ALOTTED FOR
 A TCO. TWO 30 DAYS EXTENTIONS MAY BE
 GRANTED ALLOWING A 90 DAY WINDOW TO
 COMPLETE THE 2ND PHASE.
 TWO SEPERATE PERMITS MAY BE THE
 SOLUTION, ONE FOR THE NEW WORK WITH THE
 TWO HR WALL INCLUDED A SECOND FOR THE
 REMODEL OF THE EXISTING BUILDING AND
 ADDITION TO THE EXISTING LIBRARY.
 3B) THE SECOND CONCERN IS WHEN WORK IN
 PHASE I HAS COMMENCED WILL THE EXISTING
 LIBRARY STILL BE USED? IF SO INDICATE
 EGRESS TO AND FROM BUILDING VS WORK AND
 STORAGE AREAS OF PHASE I.
 3C) THE THIRD MAJOR CONCERN WILL BE
 HOW THE SMOKE CONTROL FOR THE ATRIUM
 WILL WORK. PHASE INDICATES THE USE OF
 SMOKE CONTROL, BUTWHEN PHASE II IS
 COMPLETE AND THE TEMPORARY WALL IS DOWN
 THE PHAASE 1 & PHASE II WILL MAKE ONE
 LARGE ATTRIUM WITH NO SMOKE CONTROL
 INDICATED FOR THE OCTOGON PORTION OF
 THE
  
 ATRIUM.
 3D) THE FOURTH CONCERN WOULD BE THAT
 PHASE I BE COMPLETED AND THE COLLEGE
 DECIDE NOT TO DO PHASE II THUS
 REQUIRING
 NOT A 2 HR WALL BUT A 4HR WITH PROBLEMS
  
 DEALING WITH EGRESS. THERE IS NO
 INSURANCE PHASE II WILL HAPPEN.
 POSSIBLY
 POST A BOND FOR PHASE II AGAIN UNDER A
 SEPERATE PERMIT.
  
 4)SHEET A1.02, THE NORTH STAIRWELL DOOR
 1S1,THERE IS NO FIRE RATING.
  
 5) SHEET S-1 NOT SHOWN ON DOOR
 SCHEDULE.
  
 6) SHEET A7.01 DETAILS 1-4 NORTH
 STAIRWELL TOWER: WINDOWS (L&M) REQUIRE
 RATING 1006.1.3.2.
  
 7)SHEET A 2.03 BUTT GLAZING:
 PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 2001 FBC 2406.2.
  
 8) 11-4.4.2 HEAD ROOM. WALKS, HALLS,
 CORRIDORS, PASSAGEWAYS, AILES OR OTHER
 CIRCULATION SPACES SHALL HAVE 80 INCHES
 MINIMUM CLEAR HEAD ROOM (SEE FIGURE
 8(A)). IF VERTICAL CLEARENCE OF AN AREA
 ADJOINING AN ACCESSIBLE ROUTE IS
 REDUCED
 TO LESS THAN 80 IN. (NOMINAL
 DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY IMPARED PERSONS SHALL BE
 PROVIDED. (SEE FIGURE 8(C-1)). SEE
 STAIRWELL# 1 FIRST FLOOR.
  
 9) PLEASE INDICATE THE EXITING FOR
 STAIRWELL# 2, ELEVATOR# 2 AND THE GRAND
 STAIRWAY LEADING TO THE OCTOGON PORTION
 (PHASE II) OF THE BUILDING.
  
 10) A2.00 MISSING WALL CONNECTIONS FOR
 FLOOR TO FLOOR/ ALSO BLOCK CONNECTION
 "SEE STR"? NOT INDICATED WHERE.
  
 11) A7.04 STAIR S-A MISSING THE
 HORIZONTAL HANDRAIL EXTENSION.SEE
 11-4.9.4 HANDRAILS, FIGURE 19(C&D).
  
 12) 1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 13) 2405.5.1.1 RAILINGS, THE PANELS AND
 THEIR SUPPORT SYSTEM SHALL BE DESIGNED
 TO WITHSTAND THE LOADS SPECIIED IN
 1608.2.1 AND 1608.2.2. ASAFETY FACTOR
 OF
 4 SHALL BE USED. PROVIDE CALCULATIONS
  
 14) A1.02/ A7.03 DETAIL O 1007.5.9
 HANDRAILS FOR MONUMENTAL STAIRS,
 HANDRAILS SHALL BE LOCATED ALONG THE
 MOST DIRECT PATH OF EGRESS TRAVEL.
  
 15) S0.02 OCTOGON, BASEMENT , ARE ALL
 OF
 THE COLUMNS REMOVED OR ONLY (2).
  
 16) S0.03 OCTOGON- LEVEL 1 DEMO PLAN
 INDICATES EXISTING HORIZONTAL STEEL
 BEAMS TO REMAIN, BUT HOW DO YOU SPAN
 THE
 GRID AREA WHERE THE STEEL COLUMNS WERE
 REMOVED? HOW DOES THE HORIZONTAL STEEL
 BRIDGE THIS SIMPLE SPAN CONFIGURATION?
  
 17A) S1.09 A) THE AREA BEHIND THE
 OCTOGON STRUCTURE, THERE IS NO FRAMING
 INFORMATION.
 17B) FINISH NOTE: HSS_ _ X_ _X_ _ @
 4'-0" C/C MAX?
  
 18) PLANS TO INDICATE READING, STUDY
 AREAS, CARD CATALOG, MAGAZINE DISPLAY
 AND A MINIMUM OF 42" BETWEEN STACKS-
 FBC 11-8 (1-5).
  
 19) A1.04 ROOM 204, 2" GATE MISSING THE
 18" ON THE LATCH SIDE OF GATE SEE:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING
 CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 20) A1.08 LEVEL 4 NOTE A4.03 DETAIL 8,
 THE PLAN DOES NOT PROVIDE FRAMING
 INFORMATION HOW TO BUILD ARCH? ALSO
 PROVIDE FINISH MATERIAL INFORMATION FOR
 ACOUSTIC BOARD
  
 21) A4.04 DETAILS MISSING PAGE AND
 DETAIL NUMBER.
  
 22) 1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF
 SURFACE.
  
 23) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 24) 1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 25) S0.00 LIVE LOADS J(5) WIND SPEED
 145 CORRECT,FIGURE 1606 WIND-BORNE
 DEBRIS REGION; INDICATES THAT W.P.B.
 CITY OF IS LOCATED IN THE 140 MPH ZONE.
 PLANS ARE TO INDICATE THIS.
  
 26) CORRECT EXPOSURE TO "B"
  
 27) IMPORTANCE FACTOR WHEN OCCUPANT LOAD
 IS OVER 300 INA SINGLE ROOM THE
 IMPORTANCE FACTOR BECOMES 1.15.
  
 28) INDICATE ON ELEVATIONS THE INTERIOR
 ZONES AND END ZONES WITH RESPECTIVE
 POSITIVE AND NEGATIVE PRESSURES.
  
  
 29)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR WINDOWS
 B) EXTERIOR GLAZED DOORS
 C)EXTERIOR SOLID OR LOUVERED DOORS
 D) MULLIONS
 E) LOUVERS
 F)STORM SHUTTERS
 G) SOFFITS
 H) COMPONENTS & CLADDING
 1) TRUSS ANCHORS
 2)RAILINGS
 I) ROOFING PRODUCTS AND ASSEMBLIES
  
 30) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 31) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 32)1707.4.5.2 MULLIONS SHALL BE
 DESIGN- ED TO TRANSFER THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW OR
 DOOR ASSEMBLIES TO THE ROUGH OPENING
 SUBTRATE.
  
 33) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A2.05 DETAIL# 30 INDICATES THE USE
 OF NAILABLE INSULATION, PROVIDE THE
 PRODUCT APPROVAL AND WHAT THE POSITIVE
 AND NEGATIVEPRESSURESBEFORETILE
 WITHDRAW.
  
 34) ENGINEER TO PROVIDE ATTACHMENT OF
 ROOF SHEATHING FOR VARIOUS ROOF PRESSURE
 ZONES, ZONE 1, 2 &3. IF THE SUBMITTED
 PRODUCT APPROVALS HAVE A LIMITATION FOR
  
 ENHANCED NAILING ZONES THIS INFORMATION
 TO ALSO BE SUBMITTED.
  
 35) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THE ANSWERS TO THIS REVIEW MAY RESULT IN
  
 ADDTIONAL QUESTIONS NOT ADDRESSED UNDER
 THIS PLAN REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026