Date |
Text |
2004-12-22 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04111073 |
| ADD: 300 PEMBROKE PLACE |
| CONT: THE WEITZ CO |
| TEL: (561)310-2723 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| |
| NOTES: SINCE THIS PROJECT IS A |
| THRESHOLD |
| |
| BUILDING (3) COPIES OF ALL PLANS, |
| PRODUCT APPROVALS & SUBMITTALS WILL BE |
| REQUIRED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT |
| NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR |
| SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE |
| FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1)W.P.B. AMENDMENT 105.13.4.4 ALL |
| PLANS FOR THE BUILDING WHICH ARE |
| REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CON- |
| TAIN A STATEMENT THAT, TO THE BEST OF |
| THE ARCHITECT'S PR ENGINEER'S |
| KNOWLEDGE, |
| THE PLANS AND SPECIFICATIONS COMPLY |
| WITH |
| THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 2) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 3)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| PHASING I/ II. THERE ARE VARIOUS ISSUES |
| THAT WILL NEED TO BE ADDRESSED BEFORE |
| PHASING WILL BE APPROVED VS. APPROVAL |
| FOR A SEPERATE PERMIT FOR A REMODELING |
| AND ADDITION PREMIT FOR THE WORK TO BE |
| ACCOMPLISHED UNDER PHASE II. |
| 3A) I DO NOT BELIEVE AFTER THE WORK |
| COMPLETED UNDER PHASE I AND A TCO( |
| PARTIAL AND OR CONDITIONAL CERTIFICATE |
| OF OCCUPANCY)IS ISSUED, THE WORK ON THE |
| SECOND PHASE CAN BE COMPLETED WITHIN |
| THE |
| 30 DAYS ALOTTED FOR |
| A TCO. TWO 30 DAYS EXTENTIONS MAY BE |
| GRANTED ALLOWING A 90 DAY WINDOW TO |
| COMPLETE THE 2ND PHASE. |
| TWO SEPERATE PERMITS MAY BE THE |
| SOLUTION, ONE FOR THE NEW WORK WITH THE |
| TWO HR WALL INCLUDED A SECOND FOR THE |
| REMODEL OF THE EXISTING BUILDING AND |
| ADDITION TO THE EXISTING LIBRARY. |
| 3B) THE SECOND CONCERN IS WHEN WORK IN |
| PHASE I HAS COMMENCED WILL THE EXISTING |
| LIBRARY STILL BE USED? IF SO INDICATE |
| EGRESS TO AND FROM BUILDING VS WORK AND |
| STORAGE AREAS OF PHASE I. |
| 3C) THE THIRD MAJOR CONCERN WILL BE |
| HOW THE SMOKE CONTROL FOR THE ATRIUM |
| WILL WORK. PHASE INDICATES THE USE OF |
| SMOKE CONTROL, BUTWHEN PHASE II IS |
| COMPLETE AND THE TEMPORARY WALL IS DOWN |
| THE PHAASE 1 & PHASE II WILL MAKE ONE |
| LARGE ATTRIUM WITH NO SMOKE CONTROL |
| INDICATED FOR THE OCTOGON PORTION OF |
| THE |
| |
| ATRIUM. |
| 3D) THE FOURTH CONCERN WOULD BE THAT |
| PHASE I BE COMPLETED AND THE COLLEGE |
| DECIDE NOT TO DO PHASE II THUS |
| REQUIRING |
| NOT A 2 HR WALL BUT A 4HR WITH PROBLEMS |
| |
| DEALING WITH EGRESS. THERE IS NO |
| INSURANCE PHASE II WILL HAPPEN. |
| POSSIBLY |
| POST A BOND FOR PHASE II AGAIN UNDER A |
| SEPERATE PERMIT. |
| |
| 4)SHEET A1.02, THE NORTH STAIRWELL DOOR |
| 1S1,THERE IS NO FIRE RATING. |
| |
| 5) SHEET S-1 NOT SHOWN ON DOOR |
| SCHEDULE. |
| |
| 6) SHEET A7.01 DETAILS 1-4 NORTH |
| STAIRWELL TOWER: WINDOWS (L&M) REQUIRE |
| RATING 1006.1.3.2. |
| |
| 7)SHEET A 2.03 BUTT GLAZING: |
| PROVIDE ENGINEERING FOR BUTT GLASS |
| ASSEMBLIES PER 2001 FBC 2406.2. |
| |
| 8) 11-4.4.2 HEAD ROOM. WALKS, HALLS, |
| CORRIDORS, PASSAGEWAYS, AILES OR OTHER |
| CIRCULATION SPACES SHALL HAVE 80 INCHES |
| MINIMUM CLEAR HEAD ROOM (SEE FIGURE |
| 8(A)). IF VERTICAL CLEARENCE OF AN AREA |
| ADJOINING AN ACCESSIBLE ROUTE IS |
| REDUCED |
| TO LESS THAN 80 IN. (NOMINAL |
| DIMENSION), A BARRIER TO WARN BLIND OR |
| VISUALLY IMPARED PERSONS SHALL BE |
| PROVIDED. (SEE FIGURE 8(C-1)). SEE |
| STAIRWELL# 1 FIRST FLOOR. |
| |
| 9) PLEASE INDICATE THE EXITING FOR |
| STAIRWELL# 2, ELEVATOR# 2 AND THE GRAND |
| STAIRWAY LEADING TO THE OCTOGON PORTION |
| (PHASE II) OF THE BUILDING. |
| |
| 10) A2.00 MISSING WALL CONNECTIONS FOR |
| FLOOR TO FLOOR/ ALSO BLOCK CONNECTION |
| "SEE STR"? NOT INDICATED WHERE. |
| |
| 11) A7.04 STAIR S-A MISSING THE |
| HORIZONTAL HANDRAIL EXTENSION.SEE |
| 11-4.9.4 HANDRAILS, FIGURE 19(C&D). |
| |
| 12) 1608.2.3 THE GUARDRAIL SYSTEM SHALL |
| BE DESIGNED AND CONSTRUCTED TO RESIST A |
| 200 LB CONCENTRATED HORIZONTAL LOAD |
| APPLIED ON A 1 SQ FT AREA AT ANY POINT |
| IN THE SYSTEM INCLUDING INTERMEDIATE |
| RAILS OR OTHER ELEMENTS SERVING THIS |
| PURPOSE. |
| |
| 13) 2405.5.1.1 RAILINGS, THE PANELS AND |
| THEIR SUPPORT SYSTEM SHALL BE DESIGNED |
| TO WITHSTAND THE LOADS SPECIIED IN |
| 1608.2.1 AND 1608.2.2. ASAFETY FACTOR |
| OF |
| 4 SHALL BE USED. PROVIDE CALCULATIONS |
| |
| 14) A1.02/ A7.03 DETAIL O 1007.5.9 |
| HANDRAILS FOR MONUMENTAL STAIRS, |
| HANDRAILS SHALL BE LOCATED ALONG THE |
| MOST DIRECT PATH OF EGRESS TRAVEL. |
| |
| 15) S0.02 OCTOGON, BASEMENT , ARE ALL |
| OF |
| THE COLUMNS REMOVED OR ONLY (2). |
| |
| 16) S0.03 OCTOGON- LEVEL 1 DEMO PLAN |
| INDICATES EXISTING HORIZONTAL STEEL |
| BEAMS TO REMAIN, BUT HOW DO YOU SPAN |
| THE |
| GRID AREA WHERE THE STEEL COLUMNS WERE |
| REMOVED? HOW DOES THE HORIZONTAL STEEL |
| BRIDGE THIS SIMPLE SPAN CONFIGURATION? |
| |
| 17A) S1.09 A) THE AREA BEHIND THE |
| OCTOGON STRUCTURE, THERE IS NO FRAMING |
| INFORMATION. |
| 17B) FINISH NOTE: HSS_ _ X_ _X_ _ @ |
| 4'-0" C/C MAX? |
| |
| 18) PLANS TO INDICATE READING, STUDY |
| AREAS, CARD CATALOG, MAGAZINE DISPLAY |
| AND A MINIMUM OF 42" BETWEEN STACKS- |
| FBC 11-8 (1-5). |
| |
| 19) A1.04 ROOM 204, 2" GATE MISSING THE |
| 18" ON THE LATCH SIDE OF GATE SEE: |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING |
| CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARENCES SHALL BE |
| CLEAR & LEVEL. |
| |
| 20) A1.08 LEVEL 4 NOTE A4.03 DETAIL 8, |
| THE PLAN DOES NOT PROVIDE FRAMING |
| INFORMATION HOW TO BUILD ARCH? ALSO |
| PROVIDE FINISH MATERIAL INFORMATION FOR |
| ACOUSTIC BOARD |
| |
| 21) A4.04 DETAILS MISSING PAGE AND |
| DETAIL NUMBER. |
| |
| 22) 1503.4.2 OVERFLOW DRAINS SHALL BE |
| THE SAME SIZE AS ROOF DRAINS, INSTALLED |
| WITH THE INLET FLOW LINE LOCATED 2" |
| ABOVE THE LOWEST POINT OF THE ROOF LINE. |
| OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| 4"IN HEIGTH AND SHALL BE PLACED IN WALLS |
| OR PARARETS WITH THE INLET FLOW LINE |
| NOT LESS THAN 2" ABOVE THE ROOF |
| SURFACE. |
| |
| 23) 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 24) 1511.7 ROOF MOUNTED MECHANICAL UNIT |
| S SHALL BE MOUNTED ON CURBS RAISED A |
| MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| FACE, OR WHERE ROOFING MATERIALS EXTEND |
| BENEATH THE UNIT, ON RAISED EQUIPMENT |
| SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| MECH. 301.13 WIND RESISTANCE MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUP PORTS THAT |
| ARE EXPOSED TO WIND SHALL BE DESIGNED |
| AND INSTALLED TO RESIST THE WIND |
| PRESSURES ON THE EQUIPMENT & THE |
| SUPPORTS AS DETERMINED IN ACCORDANCE |
| WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| LISHED BY DESIGN OR BY APPLICATION OF |
| SECTION 301.13.1. |
| |
| 25) S0.00 LIVE LOADS J(5) WIND SPEED |
| 145 CORRECT,FIGURE 1606 WIND-BORNE |
| DEBRIS REGION; INDICATES THAT W.P.B. |
| CITY OF IS LOCATED IN THE 140 MPH ZONE. |
| PLANS ARE TO INDICATE THIS. |
| |
| 26) CORRECT EXPOSURE TO "B" |
| |
| 27) IMPORTANCE FACTOR WHEN OCCUPANT LOAD |
| IS OVER 300 INA SINGLE ROOM THE |
| IMPORTANCE FACTOR BECOMES 1.15. |
| |
| 28) INDICATE ON ELEVATIONS THE INTERIOR |
| ZONES AND END ZONES WITH RESPECTIVE |
| POSITIVE AND NEGATIVE PRESSURES. |
| |
| |
| 29)1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) EXTERIOR WINDOWS |
| B) EXTERIOR GLAZED DOORS |
| C)EXTERIOR SOLID OR LOUVERED DOORS |
| D) MULLIONS |
| E) LOUVERS |
| F)STORM SHUTTERS |
| G) SOFFITS |
| H) COMPONENTS & CLADDING |
| 1) TRUSS ANCHORS |
| 2)RAILINGS |
| I) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 30) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY |
| NOT COVERED BY 1707.4.2 |
| (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| ED FOR A PERIOD EQUAL TO THE QUANITY |
| 3600/ V WHERE THE TIME PERIOD IS IN |
| SECTIONS AND V IS IN MILES PER HR TAKEN |
| FROM FIGURE 1606. THE TIME PERIOD SHALL |
| ALSO INCLUDE A 10 SECOND PERIOD AT A |
| LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| PRESSURE. DADE COUNTY & SBCCI REPORTS |
| ARE ACCEPTED. |
| |
| 31) 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 32)1707.4.5.2 MULLIONS SHALL BE |
| DESIGN- ED TO TRANSFER THE DESIGN |
| PRESSURE LOADS APPLIED BY THE WINDOW OR |
| DOOR ASSEMBLIES TO THE ROUGH OPENING |
| SUBTRATE. |
| |
| 33) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| SHEET A2.05 DETAIL# 30 INDICATES THE USE |
| OF NAILABLE INSULATION, PROVIDE THE |
| PRODUCT APPROVAL AND WHAT THE POSITIVE |
| AND NEGATIVEPRESSURESBEFORETILE |
| WITHDRAW. |
| |
| 34) ENGINEER TO PROVIDE ATTACHMENT OF |
| ROOF SHEATHING FOR VARIOUS ROOF PRESSURE |
| ZONES, ZONE 1, 2 &3. IF THE SUBMITTED |
| PRODUCT APPROVALS HAVE A LIMITATION FOR |
| |
| ENHANCED NAILING ZONES THIS INFORMATION |
| TO ALSO BE SUBMITTED. |
| |
| 35) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| THE ANSWERS TO THIS REVIEW MAY RESULT IN |
| |
| ADDTIONAL QUESTIONS NOT ADDRESSED UNDER |
| THIS PLAN REVIEW. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |