Plan Review Notes
Plan Review Notes For Permit 04111066
Permit Number 04111066
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-24 00:00:00 
 ********** UNSAT ************
  
 1)NOTE: PLEASE SEE WIRING DIAGRA, SHOWS
 30A FOR 1HP BLOWER AND 40A FOR 1 1/2 HO
 PUMP??
 PLEASE SEE 430.151(TABLES) FOR LOADS OF
 PUMPS.
 MIN OCP AND MAX OCP 430.52 ETC.
 PLEASE ALSO SEE 310.16 FOR AWG AND 240.4
 FOR PROTECTION OF CONDUCTORS.
  
 3)NOTE: PLEASE SEE BLDG REVIEW FOR
 VALUATION PER FBC 104.6.5.
 VALUE IS TO INCLUDE ALL LABOR AND
 MATERIALS EVEN IF OWNER SUPPLIED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]