Plan Review Notes For Permit 04110897 |
Permit Number |
04110897 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-05-13 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)SEE PREVIOUS LIST, ITEM #2. | | PRESSURES REQUESTED BY PREVIOUS REVIEWER | | NOT PROVIDED.NO ATTACHMENT DETAIL | | SHOWN. | | | | 2.)SHEET 5 OF 6, GENERAL NOTES, STATES | | THAT THE CABINET WEIGHT SHALL NOT EXCEED | | 10962.AREN'T THE CABINETS EXISTING? | | WHERE IS THE GENERATOR WEIGHT ADDRESSED? | | | | 3.)SEE PREVIOUS LIST, ITEM #3. | | VALUATION IS TOO LOW. | | | | 4.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 5.)THE NOTES REFER TO CUTTING OF THE | | SLAB, CONFIRMING POST TENSION CABLE | | LOCATIONS, CUTTING AND PATCHING OF THE | | ROOF.THE PLANS SHOULD INCLUDE ONLY | | WORK DONE UNDER THIS PERMIT.IF THESE | | THINGS ARE BEING DONE, PLEASE SHOW ON | | THE PLAN. | | | | 6.)THE APPLICATION REFERS TO A 12 KW | | GENERATOR, PLANS SHOW 30KW. |
|