2005-05-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #2.
 PRESSURES REQUESTED BY PREVIOUS REVIEWER
 NOT PROVIDED.NO ATTACHMENT DETAIL
 SHOWN.
  
 2.)SHEET 5 OF 6, GENERAL NOTES, STATES
 THAT THE CABINET WEIGHT SHALL NOT EXCEED
 10962.AREN'T THE CABINETS EXISTING?
 WHERE IS THE GENERATOR WEIGHT ADDRESSED?
  
 3.)SEE PREVIOUS LIST, ITEM #3.
 VALUATION IS TOO LOW.
  
 4.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 5.)THE NOTES REFER TO CUTTING OF THE
 SLAB, CONFIRMING POST TENSION CABLE
 LOCATIONS, CUTTING AND PATCHING OF THE
 ROOF.THE PLANS SHOULD INCLUDE ONLY
 WORK DONE UNDER THIS PERMIT.IF THESE
 THINGS ARE BEING DONE, PLEASE SHOW ON
 THE PLAN.
  
 6.)THE APPLICATION REFERS TO A 12 KW
 GENERATOR, PLANS SHOW 30KW.