Plan Review Notes
Plan Review Notes For Permit 04110897
Permit Number 04110897
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-12-20 00:00:001. PLANS DO NOT INDICATE WHAT THE
 NEW EMERGENCY GENERATOR WILL RUN.
  
 2. PLANS DO NOT INDICATE HOW AND WHERE
 THE CONDUITS WILL RUN.
  
 3. THE GAS LINE SHOWN ON THE PLANS
 TERMINATES WHERE.
  
 4. NO PRODUCT APPROVAL GIVEN FOR
 THE NEW PROPOSED GENERATOR.
  
 5. WHAT SIZE FUEL TANK IS PROPOSED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910