Plan Review Notes
Plan Review Notes For Permit 04110889
Permit Number 04110889
Review Stop P
Sequence Number 1
Notes
Date Text
2004-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SUBMIT A DETAIL FOR THE BREAK AREA
 SINK PER SECTION 11-4.24 AND ALL
 SUBSECTIONS. SHOW THE FOLLOWING INFO.
 11-4.24.2 HEIGHT
 11-4.24.3 KNEE CLEARANCE
 11-4.24.4 SINK DEPTH
 11-4.24.5 CLEAR FLOOR SPACE - FORWARD
 APPROACH REQUIRED. NO DOORS OR SHELVES.
 11-4.24.6 EXPOSED PIPES AND SURFACES
 11-4.24.7 FAUCETS
 2) SHT M-1 SUBMIT A WATER RISER DIAGRAM
 PER SECTION 104.3.1.1. SHOW ALL PIPE
 SIZES.
 3) ARCHITECT TITLE BLOCK MISSING
 INFORMATION. SEE FAC 61G1-16.004(2)(6)
 FS 481.219 & FS 481.2055
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]