Plan Review Notes For Permit 04110889 |
Permit Number |
04110889 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-12-17 00:00:00 | DENIED: | | 1.RETURN AIR REQUIRED FROM THE OFFICE, | | CONFERENCE ROOM, AND INVENTORY AREAS. | | | | 2.PLEASE CLARIFY THE MEZZINE LEVEL. | | IT APPEARS TO OPEN TO THE RECEPTION | | AREA.IF THIS IS NOT THE CASE, A RETURN | | AIR WILL BE REQUIRED FROM THE | | RECEPTION/SHOWROOM AREAS. | | | | 3.PLAN SHEET M-2 GENERAL HVAC NOTE | | #12, INDICATES A NEW EXHAUST FAN ROUTED | | TO EXTERIOR WALL.PLEASE INDICATE | | LOCATION OF THE NEW FAN AND PROVIDE | | SCHEDULE INDICATING ALL PERTINENT | | INFORMATION. | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | WITH NOTIFICATION TO ALARM/STROBE IS | | REQUIRED PER 2001 FBC(M)606.2.1 AND | | 606.4.1 EXCEPTION #2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | |
|