2004-12-17 00:00:00DENIED:
 1.RETURN AIR REQUIRED FROM THE OFFICE,
 CONFERENCE ROOM, AND INVENTORY AREAS.
  
 2.PLEASE CLARIFY THE MEZZINE LEVEL.
 IT APPEARS TO OPEN TO THE RECEPTION
 AREA.IF THIS IS NOT THE CASE, A RETURN
 AIR WILL BE REQUIRED FROM THE
 RECEPTION/SHOWROOM AREAS.
  
 3.PLAN SHEET M-2 GENERAL HVAC NOTE
 #12, INDICATES A NEW EXHAUST FAN ROUTED
 TO EXTERIOR WALL.PLEASE INDICATE
 LOCATION OF THE NEW FAN AND PROVIDE
 SCHEDULE INDICATING ALL PERTINENT
 INFORMATION.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IS
 REQUIRED PER 2001 FBC(M)606.2.1 AND
 606.4.1 EXCEPTION #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  