Plan Review Notes
Plan Review Notes For Permit 04110889
Permit Number 04110889
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 713.13 F.S.A NOTICE OF
 COMMENCEMENT SHALL BE RECORDED AT PALM
 BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT
 CAN BE ISSUED. BLANK FORMS ARE AVAILABLE
 FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST
 BE RE-RECORDED IF THE DESCRIBED
 IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT
 SHALL
 INCLUDE A TITLE BLOCK WITH THE PRINTED
 NAME OF THE ARCHITECT SEALING THE
 PLANS.
 THIS MAY BE ADDED BY HAND.
  
 3) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION (COA#)
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
 NOTE:DBPR RECORDS SHOW A COA# OF
 AA26000848 FOR A 'DOING BUSINESS UNDER'
 (DBA) NAME OF NEXUSARCHITECTURE, INC.
 BUT THE PLANS SHOW NEXUS DESIGN GROUP,
 LLC.THE PLANS SHALL REFLECT THE NAME
 OF THE LICENSED FIRM.
  
 4) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5) FBC 1005.7.3SHEET A-1, MEZZANINE.
 AS THE EGRESS STAIRWAY FROM THE
 MEZZANINE IS OPEN AND DESCENDS INTO THE
 FIRST FLOOR ROOM, THE SPACE BENEATH THE
 MEZZANINE IS ONLY PERMITTED TO BE
 ENCLOSED IF IT IS PROTECTED THOUGHOUT
 BY
 SMOKE DETECTION, IN ACCORDANCE WITH
 NFPA 72, THAT SOUNDS AN ALARM ON THE
 MEZZANINE.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 6) FBC 1608.2.1SHEET A-1, THE
 HANDRAIL SHALL BE DESIGNED AND
 CONSTRUCTED FOR A CONCENTRATED LOAD OF
 200 LB AND A LINE LOAD OF 50 PLF.THESE
 LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY BUT SHALL BE APPLIED
 INDIVIDUALLY AT ANY POINT, AND IN ANY
 DIRECTION, TO PRODUCE MAXIMUM STRESS IN
 EACH OF THE COMPONENTS OR SUPPORTS.
 AMEND/ANNOTATE THE PLANS TO SPECIFY
 THESE LOADS. IT IS NOTED THAT THE
 ARCHITECTURAL PLANS REFER TO THE
 STRUCTURAL PLANS AND VICE VERSA, BUT
 NEITHER PLAN PROVIDES DETAILS.
  
 7) FBC 1608.2.2 SHEET A-1, THE
 GUARDRAIL SHALL BE DESIGNED AND
 CONSTRUCTED FOR A CONCENTRATED LOAD OF
 200 LB APPLIED IN ANY DIRECTION AT THE
 TOP OF THE GUARDRAIL, A CONCENTRATED
 HORIZONTAL LOAD OF 200 LB APPLIED ON A 1
 SQ FT AREA AT ANY POINT, AND A LINE LOAD
 OF 50 PLF APPLIED HORIZONTALLY AT THE
 REQUIRED GUARDRAIL HEIGHT WITH A
 SIMULTANEOUS LINE LOAD OF 100 PLF
 APPLIED VERTICALLY DOWNWARD ON THE TOP
 OF THE GUARDRAIL. THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY (UNLESS NOTED
 ABOVE) BUT SHALL BE APPLIED INDIVIDUALLY
 TO PRODUCE MAXIMUM STRESS IN EACH OF
 THE
 COMPONENTS OR SUPPORTS.
 AMEND/ANNOTATE THE PLANS TO SPECIFY
 THESE LOADS. IT IS NOTED THAT THE
 ARCHITECTURAL PLANS REFER TO THE
 STRUCTURAL PLANS AND VICE VERSA, BUT
 NEITHER PLAN PROVIDES DETAILS.
  
 8) FBC 11-4.24SHEET A-1, THE BREAKROOM
 SINK SHALL COMPLY WITH ALL OF THE
 ACCESSIBILTY REQUIREMENTS FOR RIM
 HEIGHT, KNEE CLEARANCE, BOWL DEPTH,
 CLEAR FLOOR SPACE, HOT WATER PIPE
 ISOLATION AND FAUCETS.AMEND THE PLANS
 TO DEMONSTRATE COMPLIANCE.
  
 9) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]