2004-12-22 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) 713.13 F.S.A NOTICE OF |
| COMMENCEMENT SHALL BE RECORDED AT PALM |
| BEACH COUNTY COURTHOUSE AND A COPY |
| SUBMITTED TO THIS OFFICE BEFORE A PERMIT |
| CAN BE ISSUED. BLANK FORMS ARE AVAILABLE |
| FROM THIS OFFICE. |
| NOTE: THE NOTICE OF COMMENCEMENT MUST |
| BE RE-RECORDED IF THE DESCRIBED |
| IMPROVEMENT OR CONSTRUCTION IS NOT |
| COMMENCED WITHIN 90 DAYS OF RECORDING. |
| |
| 2) 61G1-16.004FL. ADMIN. CODE.PLANS |
| PREPARED BY A REGISTERED ARCHITECT |
| SHALL |
| INCLUDE A TITLE BLOCK WITH THE PRINTED |
| NAME OF THE ARCHITECT SEALING THE |
| PLANS. |
| THIS MAY BE ADDED BY HAND. |
| |
| 3) 481.219 F.S.CERTIFICATE OF |
| AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| SHEET BEARING THE NAME OF AN ARCHITECT |
| PRACTICING UNDER A FICTITIOUS NAME, A |
| CORPORATION, OR A PARTNERSHIP, OFFERING |
| ARCHITECTURAL SERVICES, SHALL INCLUDE |
| THE CERTIFICATE OF AUTHORIZATION (COA#) |
| NUMBER.ADD THE NUMBER TO EACH SHEET. |
| THIS MAY BE ADDED BY HAND. |
| NOTE:DBPR RECORDS SHOW A COA# OF |
| AA26000848 FOR A 'DOING BUSINESS UNDER' |
| (DBA) NAME OF NEXUSARCHITECTURE, INC. |
| BUT THE PLANS SHOW NEXUS DESIGN GROUP, |
| LLC.THE PLANS SHALL REFLECT THE NAME |
| OF THE LICENSED FIRM. |
| |
| 4) FBC 13-103.1.2BEFORE A BUILDING |
| PERMIT CAN BE ISSUED, THE SUBMITTED |
| ENERGY CODE COMPLIANCE FORMS SHALL BE |
| SIGNED BY THE BUILDING OWNER, THE |
| OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| AGENT LEGALLY DESIGNATED BY THE OWNER. |
| |
| 5) FBC 1005.7.3SHEET A-1, MEZZANINE. |
| AS THE EGRESS STAIRWAY FROM THE |
| MEZZANINE IS OPEN AND DESCENDS INTO THE |
| FIRST FLOOR ROOM, THE SPACE BENEATH THE |
| MEZZANINE IS ONLY PERMITTED TO BE |
| ENCLOSED IF IT IS PROTECTED THOUGHOUT |
| BY |
| SMOKE DETECTION, IN ACCORDANCE WITH |
| NFPA 72, THAT SOUNDS AN ALARM ON THE |
| MEZZANINE.ANNOTATE THE PLANS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 6) FBC 1608.2.1SHEET A-1, THE |
| HANDRAIL SHALL BE DESIGNED AND |
| CONSTRUCTED FOR A CONCENTRATED LOAD OF |
| 200 LB AND A LINE LOAD OF 50 PLF.THESE |
| LOADS SHALL NOT BE APPLIED |
| SIMULTANEOUSLY BUT SHALL BE APPLIED |
| INDIVIDUALLY AT ANY POINT, AND IN ANY |
| DIRECTION, TO PRODUCE MAXIMUM STRESS IN |
| EACH OF THE COMPONENTS OR SUPPORTS. |
| AMEND/ANNOTATE THE PLANS TO SPECIFY |
| THESE LOADS. IT IS NOTED THAT THE |
| ARCHITECTURAL PLANS REFER TO THE |
| STRUCTURAL PLANS AND VICE VERSA, BUT |
| NEITHER PLAN PROVIDES DETAILS. |
| |
| 7) FBC 1608.2.2 SHEET A-1, THE |
| GUARDRAIL SHALL BE DESIGNED AND |
| CONSTRUCTED FOR A CONCENTRATED LOAD OF |
| 200 LB APPLIED IN ANY DIRECTION AT THE |
| TOP OF THE GUARDRAIL, A CONCENTRATED |
| HORIZONTAL LOAD OF 200 LB APPLIED ON A 1 |
| SQ FT AREA AT ANY POINT, AND A LINE LOAD |
| OF 50 PLF APPLIED HORIZONTALLY AT THE |
| REQUIRED GUARDRAIL HEIGHT WITH A |
| SIMULTANEOUS LINE LOAD OF 100 PLF |
| APPLIED VERTICALLY DOWNWARD ON THE TOP |
| OF THE GUARDRAIL. THESE LOADS SHALL NOT |
| BE APPLIED SIMULTANEOUSLY (UNLESS NOTED |
| ABOVE) BUT SHALL BE APPLIED INDIVIDUALLY |
| TO PRODUCE MAXIMUM STRESS IN EACH OF |
| THE |
| COMPONENTS OR SUPPORTS. |
| AMEND/ANNOTATE THE PLANS TO SPECIFY |
| THESE LOADS. IT IS NOTED THAT THE |
| ARCHITECTURAL PLANS REFER TO THE |
| STRUCTURAL PLANS AND VICE VERSA, BUT |
| NEITHER PLAN PROVIDES DETAILS. |
| |
| 8) FBC 11-4.24SHEET A-1, THE BREAKROOM |
| SINK SHALL COMPLY WITH ALL OF THE |
| ACCESSIBILTY REQUIREMENTS FOR RIM |
| HEIGHT, KNEE CLEARANCE, BOWL DEPTH, |
| CLEAR FLOOR SPACE, HOT WATER PIPE |
| ISOLATION AND FAUCETS.AMEND THE PLANS |
| TO DEMONSTRATE COMPLIANCE. |
| |
| 9) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS, TO FORM A SET OF |
| 'OLD/VOID SHEETS', FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE RESUBMITTED |
| PLANS. |
| |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |