2004-12-01 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) A SEPARATE ELECTRICAL PERMIT IS
 REQUIRED FOR THE GENERATOR. MANUF.
 SPECIFICATIONS ARE REQUIRED AS WELL AS
 SETBACKS FOR THE GAS GENERATOR AND POOL
 HEATER ON THE SURVEY FOR ZONING
 APPROVAL
 2) A SEPARATE PLUMBING PERMIT IS
 REQUIRED FOR THE HOOK-UP OF THE POOL
 HEATER TO THE POOL EQUIPMENT PIPING.
 3) THE GENERATOR, POOL HEATER AND BBQ
 GRILL COSTS DO NOT SEEM TO APPEAR ON THE
 VALUE OF THE JOB AS REQUIRED BY SECTION
 104.6.5. THE VALUE OF THE JOB SHALL
 INCLUDE ALL GAS APPLIANCES AS WELL AS
 THE VALUE OF THE GAS LINES WITH
 REGULATORS, VALVES, LP TANK ECT.
 4) THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT.
 A. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]