Plan Review Notes
Plan Review Notes For Permit 04110638
Permit Number 04110638
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING
 POOLS
  
  
 A) THE FOLLOWING INFORMATION IS REQUIRED
 ON THE PLANS FOR POOL PERMIT. PLEASE
 SUBMIT A DETAIL, MANUF. SPECIFICATIONS
 OR ADD INFORMATION TO NOTES AS
 REQUIRED.
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 3) FBC-2001 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL)
 4) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD #2938-95, BACKFLOW REQUIRED ON THE
 WATER SERVICE. (ADD TO NOTES)
 5) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 6) FBC-2001 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING AND
 FITTINGS. (ADD TO NOTES)
  
  