2004-11-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FBC 1504.1WIND RESISTANCE OF MODIFIED
 BITUMEN ROOFING SYSTEM.PAGE 15 OF THE
 SUBMITTED JOHN MANSVILLE MODIFIED
 BITUMEN ROOFING SYSTEM NOA# 01-0628.14
 STATES THAT THE MAXIMUM DESIGN PRESSURE
 FOR THE PROPOSED SYSTEM IS -52.5 PSF.
 THE DESIGN PRESSURE REQUIRED IS -80 PSF
 (REF: FIG. 9 OF RWDI WIND LOAD STUDY
 REPORT #03-1042 DATED 12/20/04
 SUBMITTED
 UNDER THE BUILDING PERMIT# 02040459).
 SUBMIT A PRODUCT APPROVAL FOR A ROOFING
 SYSTEM WITH A DESIGN PRESSURE OF -80
 PSF
 OR BETTER.IT IS NOTED THAT GENERAL
 LIMITATION #7, ON PAGE 22 OF THE NOA,
 ALLOWS ENHANCED UPLIFT PRESSURES AT
 CORNERS AND PERIMETER IF FASTENER
 DENSITIES ARE INCREASED.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS