Plan Review Notes
Plan Review Notes For Permit 04110390
Permit Number 04110390
Review Stop E
Sequence Number 3
Notes
Date Text
2006-02-03 00:00:00************ UNSAT ************
  
  
 1)NOTE:*** PLEASE KNOW, A "PROVISO" WAS
 GIVEN ON JAN 31, OF 2005 FOR PLANS AND
 LOAD CALCULATIONS TO BE REVISED ALONG
 WITH ANY OTHER REVISIONS BEFORE ROUGH.
 THIS WAS NOT DONE.
 PLEASE SEE THERE ARE MANY REVISIONS TO
 PLANS WHICH WERE NEVER SUBMITTED.
 PLANS ARE NOW ONLY COMING IN FOR
 REVISIONS ONE YEAR TO DATE.
 ** PLEASE SEE THE FOLLOWING COMMENTS AS
 SOME LOADS HAVE INCREASED, HOWEVER
 SERVICE HAS NOT.
 215.5
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM ,
 PANELS AND PLANS. PLEASE SEE PANEL "A"
 SHOWS A 2-POLE 60A BRKR FEEDING POOL
 PANEL , HOWEVER POOL PANEL IS NOW SHOWN
 AS 80A'S ON PLANS AND RISER??
 PLEASE ALSO SEE LOADS INDICATED ON PANEL
 "C" DO NOT CORRELATE WITH LOADS SHOWN ON
 PANEL "A".
 215.5
  
 3)NOTE: PLEASE SEE 220.18 FOR MIN KW
 RATING WHICH SHALL BE FIGURED FOR THE
 DRYER.
  
 4)NOTE: PLEASE SEE THAT THE MAX OCP FOR
 THE OVEN RECEPT SHALL BE 50A'S.
 PLEASE SEE OVEN IS SHOWN WIHT A RECEPT
 AND NOT HARDWIRED.
 PLEASE SEE 210.21B3
  
 4)NOTE: PLEASE CORRELATE AHU'S #1 AND #2
 KW RATINGS AS LOADS FIGURED INTO LOAD
 CALCULATIONS DO NOT MATCH WITH THE KW
 RAITNG SHOWN ON PANEL SCHEDULE(S)
 FITGURED AT 65%.
 PLEASE ALSO SEE KW RATING FOR AHU#3 DOES
 NOT CORRELATE WITH LOAD CALCULATIONS.
 215.5
  
 5)NOTE: PLEASE SEE TWO A/C COMP #1'S ARE
 SHOWN , HOWEVER A/C COMP #3 IS NOT SHOWN
 ??
 215.5
  
 6)NOTE:PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE ADJUST LOAD CALCS.
  
 7)NOTE: PLEASE SEE WHAT APPEARS TO BE A
 MISSING GFI ON KITCHEN ISLAND AS
 REQUIRED FOR ISLANDS AND SEPARATE SPACES
 SEPARATED BY SINKS ETC.
 210.52C2 AND C4.
  
 8)NOTE: PLEASE VERIFY THREE FULL SIZE
 #6'S AND #8 TO AHU'S.
 PLEASE SEEEQUIPMENT GROUNDING
 CONDUCTORS MAY BE SIZED AS SHOWN ,
 HOWEVER MAY ALSO BE SIZED PER 250.122
 IF PLANS INDICATE A #6 AND #8 FOR THE
 EQUIPMENT GRNDS, THEY WILL BE REQUIRED
 OT BE INSTALLED.
 THIS IS ONLY A NOTE:
  
 9)NOTE: PLEASE SEE CONTINUOUS LOADS
 SHALL BE FIGURED AT 125% IN PANEL
 CALCULATIONS.(POOL PUMP)
 215.3,230.42.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  