2006-02-03 00:00:00 | ************ UNSAT ************ |
| |
| |
| 1)NOTE:*** PLEASE KNOW, A "PROVISO" WAS |
| GIVEN ON JAN 31, OF 2005 FOR PLANS AND |
| LOAD CALCULATIONS TO BE REVISED ALONG |
| WITH ANY OTHER REVISIONS BEFORE ROUGH. |
| THIS WAS NOT DONE. |
| PLEASE SEE THERE ARE MANY REVISIONS TO |
| PLANS WHICH WERE NEVER SUBMITTED. |
| PLANS ARE NOW ONLY COMING IN FOR |
| REVISIONS ONE YEAR TO DATE. |
| ** PLEASE SEE THE FOLLOWING COMMENTS AS |
| SOME LOADS HAVE INCREASED, HOWEVER |
| SERVICE HAS NOT. |
| 215.5 |
| |
| 2)NOTE: PLEASE CORRELATE RISER DIAGRAM , |
| PANELS AND PLANS. PLEASE SEE PANEL "A" |
| SHOWS A 2-POLE 60A BRKR FEEDING POOL |
| PANEL , HOWEVER POOL PANEL IS NOW SHOWN |
| AS 80A'S ON PLANS AND RISER?? |
| PLEASE ALSO SEE LOADS INDICATED ON PANEL |
| "C" DO NOT CORRELATE WITH LOADS SHOWN ON |
| PANEL "A". |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE 220.18 FOR MIN KW |
| RATING WHICH SHALL BE FIGURED FOR THE |
| DRYER. |
| |
| 4)NOTE: PLEASE SEE THAT THE MAX OCP FOR |
| THE OVEN RECEPT SHALL BE 50A'S. |
| PLEASE SEE OVEN IS SHOWN WIHT A RECEPT |
| AND NOT HARDWIRED. |
| PLEASE SEE 210.21B3 |
| |
| 4)NOTE: PLEASE CORRELATE AHU'S #1 AND #2 |
| KW RATINGS AS LOADS FIGURED INTO LOAD |
| CALCULATIONS DO NOT MATCH WITH THE KW |
| RAITNG SHOWN ON PANEL SCHEDULE(S) |
| FITGURED AT 65%. |
| PLEASE ALSO SEE KW RATING FOR AHU#3 DOES |
| NOT CORRELATE WITH LOAD CALCULATIONS. |
| 215.5 |
| |
| 5)NOTE: PLEASE SEE TWO A/C COMP #1'S ARE |
| SHOWN , HOWEVER A/C COMP #3 IS NOT SHOWN |
| ?? |
| 215.5 |
| |
| 6)NOTE:PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| PLEASE ADJUST LOAD CALCS. |
| |
| 7)NOTE: PLEASE SEE WHAT APPEARS TO BE A |
| MISSING GFI ON KITCHEN ISLAND AS |
| REQUIRED FOR ISLANDS AND SEPARATE SPACES |
| SEPARATED BY SINKS ETC. |
| 210.52C2 AND C4. |
| |
| 8)NOTE: PLEASE VERIFY THREE FULL SIZE |
| #6'S AND #8 TO AHU'S. |
| PLEASE SEEEQUIPMENT GROUNDING |
| CONDUCTORS MAY BE SIZED AS SHOWN , |
| HOWEVER MAY ALSO BE SIZED PER 250.122 |
| IF PLANS INDICATE A #6 AND #8 FOR THE |
| EQUIPMENT GRNDS, THEY WILL BE REQUIRED |
| OT BE INSTALLED. |
| THIS IS ONLY A NOTE: |
| |
| 9)NOTE: PLEASE SEE CONTINUOUS LOADS |
| SHALL BE FIGURED AT 125% IN PANEL |
| CALCULATIONS.(POOL PUMP) |
| 215.3,230.42. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW. |