Plan Review Notes
Plan Review Notes For Permit 04110390
Permit Number 04110390
Review Stop B
Sequence Number 2
Notes
Date Text
2005-02-14 00:00:00BUILDING REVIEW CHECKLIST:
 1- EXTERIOR ELEVATIONS STILL DON'T SHOW
 THE CHIMNEY AS REQUESTED ON PREVIOUS
 CHECKLIST. AND, SPECIFY CHIMNEY HEIGHT
 AS REQ'D BY SEC. 2804.2.4 FBC 2001.
  
 2- FIREPLACESPECS SUBMITTED ARE FOR A
 42" WOOD BURNING FIREPLACE. SPECS
 CLEARLY INDICATE THAT ALTERATION OF
 THESE SPECS WILL VOID THE WARRANTY.
 PROVIDE MANUFACTURER'S CERTIFCATION THAT
 WARRANTY WILL NOT BE VOID IF CHIMNEY CAP
 IS INSTALLED AND PROVIDE COMPLETE SPECS
 FOR CAP CONSTRUCTION. EG: MATERIALS,
 CLEARANCES, COMPLETE FRAMING (INCLUDING
 CORNERS), ETC.SECTION 104.2.1.2 CITY
 AMENDEMNTS TO FBC 2001.
 **NOTE: ARCHITECT'S LETTER ALONE DOESN'T
 CLARIFY ISSUE. MANUFACTURER RESPONSE IS
 REQUIRED TO ASSURE PROPER AND SAFE
 FUNCTIONING OFFIREPLACE. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 3- ROOF FRAMING PLAN: A) ENTRY PORCH
 SHOWS INCORRECT TRUSS BEARING HEIHGT.
 SEE DETAILS E/6 AND G1 AND G2 OF A6.
 B) ENTRY PORCH ARE NOT ENGINEERED
 TRUSSES BUT WOOD BEAMS. REVISE AS REQ'D.
 C) DETAIL L/6 SHOWN ON BAY WINDOW WAS
 KEYED WRONG. IT SHOULD BE M/6.
 D) DETAIL M/6 DOESN'T MATCH ROOF FRAMING
 PLAN. ROOF FRAMING PLAN CALLS FOR
 MASONRY BEAM. DETAIL M/6 SHOW WOOD
 FRAMING. SPECIFY CORRECT CONNECTORS: WOD
 TO WOOD OR WOOD TO MASONRY AS REQUIRED.
 REVISE ROOF FRAMING PLAN AND DETAIL AS
 REQUIRED.
 E) SPECIFY FIREBLOCKING ON DETAIL M/6 AS
 REQUIRED. SEC. 2305.1 FBC 2001.
 F) HOW ARE 2X6 WOOD STUDS SPACED AT
 16"0.C TO FORM CHIMNEY AS SHOWN ON FRONT
 ELEVATION.
 G) REVISE ROOF LOADS. ROOF FRAMING PLAN
 CALLS FOR ATTIC STORAGE, THEN, NEED TO
 INCREASE ATTIC LIVE LOAD TO 30PSF AS
 REQ'D BY TABLE 1604.1 FBC 2001.
  
 4- DOUBLE ARCHED WINDOWS AT BEDROOM #2:
 A) SPECIFY HOW IS STEEL TUBE ATTACHED AT
 TOP AND BOTTOM.
 B) HOW IS 2X BLOCKING ATTACHED TO STEEL
 TUBE. SEC. 104.2.1.2 CITY AMENDMENTS TO
 FBC 2001.
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) FIXED WINDOWS FOR LARGER WINDOWS AS
 SHOWN ON FAMILY ROOM & LIVING ROOM.
 B) EXTERIOR SWING DOOR AT GARAGE.
  
 6- BBQ SPECS SAY "DO NOT INSTALL A GRILL
 BELOW OVERHEAD UNPROTECTED COMBUSTIBLE
 CONSTRUCTION" HOW IS THIS BBQ GOING TO
 BE INSTALLED IN THE PORCH AND FOLLOW
 MANUFACTURER SPECS.
 **NOTE: I CALLED THE MANUFACTURER AND
 THEY SAID BBQ ARE NOT INTENDED TO BE
 USED IN PORCHES. THEY SAY IS FOR
 OUTDOORS INSTALLATION ONLY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.