2005-02-14 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- EXTERIOR ELEVATIONS STILL DON'T SHOW |
| THE CHIMNEY AS REQUESTED ON PREVIOUS |
| CHECKLIST. AND, SPECIFY CHIMNEY HEIGHT |
| AS REQ'D BY SEC. 2804.2.4 FBC 2001. |
| |
| 2- FIREPLACESPECS SUBMITTED ARE FOR A |
| 42" WOOD BURNING FIREPLACE. SPECS |
| CLEARLY INDICATE THAT ALTERATION OF |
| THESE SPECS WILL VOID THE WARRANTY. |
| PROVIDE MANUFACTURER'S CERTIFCATION THAT |
| WARRANTY WILL NOT BE VOID IF CHIMNEY CAP |
| IS INSTALLED AND PROVIDE COMPLETE SPECS |
| FOR CAP CONSTRUCTION. EG: MATERIALS, |
| CLEARANCES, COMPLETE FRAMING (INCLUDING |
| CORNERS), ETC.SECTION 104.2.1.2 CITY |
| AMENDEMNTS TO FBC 2001. |
| **NOTE: ARCHITECT'S LETTER ALONE DOESN'T |
| CLARIFY ISSUE. MANUFACTURER RESPONSE IS |
| REQUIRED TO ASSURE PROPER AND SAFE |
| FUNCTIONING OFFIREPLACE. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 3- ROOF FRAMING PLAN: A) ENTRY PORCH |
| SHOWS INCORRECT TRUSS BEARING HEIHGT. |
| SEE DETAILS E/6 AND G1 AND G2 OF A6. |
| B) ENTRY PORCH ARE NOT ENGINEERED |
| TRUSSES BUT WOOD BEAMS. REVISE AS REQ'D. |
| C) DETAIL L/6 SHOWN ON BAY WINDOW WAS |
| KEYED WRONG. IT SHOULD BE M/6. |
| D) DETAIL M/6 DOESN'T MATCH ROOF FRAMING |
| PLAN. ROOF FRAMING PLAN CALLS FOR |
| MASONRY BEAM. DETAIL M/6 SHOW WOOD |
| FRAMING. SPECIFY CORRECT CONNECTORS: WOD |
| TO WOOD OR WOOD TO MASONRY AS REQUIRED. |
| REVISE ROOF FRAMING PLAN AND DETAIL AS |
| REQUIRED. |
| E) SPECIFY FIREBLOCKING ON DETAIL M/6 AS |
| REQUIRED. SEC. 2305.1 FBC 2001. |
| F) HOW ARE 2X6 WOOD STUDS SPACED AT |
| 16"0.C TO FORM CHIMNEY AS SHOWN ON FRONT |
| ELEVATION. |
| G) REVISE ROOF LOADS. ROOF FRAMING PLAN |
| CALLS FOR ATTIC STORAGE, THEN, NEED TO |
| INCREASE ATTIC LIVE LOAD TO 30PSF AS |
| REQ'D BY TABLE 1604.1 FBC 2001. |
| |
| 4- DOUBLE ARCHED WINDOWS AT BEDROOM #2: |
| A) SPECIFY HOW IS STEEL TUBE ATTACHED AT |
| TOP AND BOTTOM. |
| B) HOW IS 2X BLOCKING ATTACHED TO STEEL |
| TUBE. SEC. 104.2.1.2 CITY AMENDMENTS TO |
| FBC 2001. |
| |
| 5- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) FIXED WINDOWS FOR LARGER WINDOWS AS |
| SHOWN ON FAMILY ROOM & LIVING ROOM. |
| B) EXTERIOR SWING DOOR AT GARAGE. |
| |
| 6- BBQ SPECS SAY "DO NOT INSTALL A GRILL |
| BELOW OVERHEAD UNPROTECTED COMBUSTIBLE |
| CONSTRUCTION" HOW IS THIS BBQ GOING TO |
| BE INSTALLED IN THE PORCH AND FOLLOW |
| MANUFACTURER SPECS. |
| **NOTE: I CALLED THE MANUFACTURER AND |
| THEY SAID BBQ ARE NOT INTENDED TO BE |
| USED IN PORCHES. THEY SAY IS FOR |
| OUTDOORS INSTALLATION ONLY. |
| |
| |