2004-12-08 00:00:00 | CHECKLIST: |
| 1-AREA CALCS ON SHEET A1 DON'T ADD UP |
| CORRECTLY. REVISE AS REQUIRED. |
| |
| 2-REVISE DETAILS C1 AND C2 ON SHEET A6 |
| TO MATCH ACTUAL CONDITIONS SHOWN ON |
| ROOF |
| FRAMING PLAN. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 3-PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR CANTILEVERED BEAM AT |
| BREAKFAST AREA. SPECIFY HOW ARE PRECAST |
| LINTELS JOINED AT THE 45 DEGREE ANGLE |
| AND HOW ARE THEY ATTACHED TO THE ENDS |
| TO |
| TRANSFER THE ROOF LOADS TO THE COLUMNS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| 4-FOUNDATION PLAN AND FLOOR PLAN DON'T |
| MATCH. SEE LOCATION OF BBQ. ALSO, SHOW |
| WHERE IS BBQ SUPPORTED ON?. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 5-PROVIDE COMPLY SECTION/DETAIL FOR BAY |
| WINDOW AT GARAGE AREA. SPECIFY ALL |
| MATERIALS AND FASTENERS. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| |
| 6-SHEET A3: A) REVISE ROOF SHEATHING |
| NOTE. SEE FIGURE 1606.2(C) FBC 2001 AND |
| CLEARLY IDENTIFY ALL ZONES CONSIDERED |
| TO |
| BE ZONE 3. (NOT JUST THE 4 CORNERS). |
| B) REVISE ROOF LOADS CHART. SEE TABLE |
| 1604.1 FBC 2001. |
| **NOTE: KEEP IN MIND THAT ROOF FRAMING |
| PLAN CALLS FOR ATTIC STORAGE. |
| |
| 7-PROVIDE DETAIL/SECTION FOR FRAMING AT |
| DOUBLE ARCHED WINDOWS MULLED TOGETHER |
| AS |
| SHOWN ON BEDROOM #2. SEC. 104.2.1.2 |
| CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 8-A) ELEVATIONS DON'T SHOW CHIMNEY. |
| B) ARCHITECT TO CHECK FIREPLACE SPECS |
| TO |
| VERIFY IF CHIMNEY ROOF CAP IS ALLOWED |
| WITHOUT INTERFERING WITH FLUE FUNCTION. |
| (NOTE: SOME COMPANIES DON'T ALLOW IT). |
| |
| 9-PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) BUTT GLAZING SYSTEM AS SHOWN ON |
| PLANS |
| B) ENTRY DOORS. |
| C) FIREPLACE UL LISTING & COMPLETE |
| SPECS |
| D) SIZE OF FIXED WINDOWS AS SHOWN ON |
| LIVING AND FAMILY ROOM AREAS. |
| E) BBQ UL LISTING AND SPECS. |
| |
| 10-PROVIDE STORM SHUTTERS PRODUCT |
| APPROVAL AND COMPLETE INFORMATION (KEY |
| PLAN, INSTALLATION SCHEDULE AND |
| SPECIFIC |
| ANCHORS) FOR BUTT GLAZING PROTECTION. |
| |
| 11-OWES $2378.71 FOR UPDATED VALUATION |
| AND RADON FEES. |
| |
| 12-SPECIFICATIONS ON ROOF FRAMING PLAN |
| FOR CHIMNEY DON'T MATCH DETAIL/SECTION |
| ON SHEET A6. REVISE AS REQUIRED. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO AT (561)805-6712. |