Plan Review Notes
Plan Review Notes For Permit 04110390
Permit Number 04110390
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-08 00:00:00CHECKLIST:
 1-AREA CALCS ON SHEET A1 DON'T ADD UP
 CORRECTLY. REVISE AS REQUIRED.
  
 2-REVISE DETAILS C1 AND C2 ON SHEET A6
 TO MATCH ACTUAL CONDITIONS SHOWN ON
 ROOF
 FRAMING PLAN. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 3-PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR CANTILEVERED BEAM AT
 BREAKFAST AREA. SPECIFY HOW ARE PRECAST
 LINTELS JOINED AT THE 45 DEGREE ANGLE
 AND HOW ARE THEY ATTACHED TO THE ENDS
 TO
 TRANSFER THE ROOF LOADS TO THE COLUMNS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 4-FOUNDATION PLAN AND FLOOR PLAN DON'T
 MATCH. SEE LOCATION OF BBQ. ALSO, SHOW
 WHERE IS BBQ SUPPORTED ON?. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5-PROVIDE COMPLY SECTION/DETAIL FOR BAY
 WINDOW AT GARAGE AREA. SPECIFY ALL
 MATERIALS AND FASTENERS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 6-SHEET A3: A) REVISE ROOF SHEATHING
 NOTE. SEE FIGURE 1606.2(C) FBC 2001 AND
 CLEARLY IDENTIFY ALL ZONES CONSIDERED
 TO
 BE ZONE 3. (NOT JUST THE 4 CORNERS).
 B) REVISE ROOF LOADS CHART. SEE TABLE
 1604.1 FBC 2001.
 **NOTE: KEEP IN MIND THAT ROOF FRAMING
 PLAN CALLS FOR ATTIC STORAGE.
  
 7-PROVIDE DETAIL/SECTION FOR FRAMING AT
 DOUBLE ARCHED WINDOWS MULLED TOGETHER
 AS
 SHOWN ON BEDROOM #2. SEC. 104.2.1.2
 CITY
 AMENDMENTS TO FBC 2001.
  
 8-A) ELEVATIONS DON'T SHOW CHIMNEY.
 B) ARCHITECT TO CHECK FIREPLACE SPECS
 TO
 VERIFY IF CHIMNEY ROOF CAP IS ALLOWED
 WITHOUT INTERFERING WITH FLUE FUNCTION.
 (NOTE: SOME COMPANIES DON'T ALLOW IT).
  
 9-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) BUTT GLAZING SYSTEM AS SHOWN ON
 PLANS
 B) ENTRY DOORS.
 C) FIREPLACE UL LISTING & COMPLETE
 SPECS
 D) SIZE OF FIXED WINDOWS AS SHOWN ON
 LIVING AND FAMILY ROOM AREAS.
 E) BBQ UL LISTING AND SPECS.
  
 10-PROVIDE STORM SHUTTERS PRODUCT
 APPROVAL AND COMPLETE INFORMATION (KEY
 PLAN, INSTALLATION SCHEDULE AND
 SPECIFIC
 ANCHORS) FOR BUTT GLAZING PROTECTION.
  
 11-OWES $2378.71 FOR UPDATED VALUATION
 AND RADON FEES.
  
 12-SPECIFICATIONS ON ROOF FRAMING PLAN
 FOR CHIMNEY DON'T MATCH DETAIL/SECTION
 ON SHEET A6. REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL